10.10 H: Terminal Functions
566 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
◆ H6: Pulse Train Input/Output
No.
(Hex.)
Name Description
Default
(Range)
Ref.
H6-01
(042C)
Terminal RP Pulse
Train Function
Sets the function for pulse train input terminal RP.
0 : Frequency Reference
1 : PID Feedback Value
2 : PID Setpoint Value
3 : Speed Feedback (V/F Control)
0
(0 - 3)
931
H6-02
(042D)
RUN
Terminal RP
Frequency Scaling
Sets the frequency of the pulse train input signal used when the
function set with H6-01 [Terminal RP Pulse Train Function] is
100%.
1440 Hz
(100 - 32000 Hz)
932
H6-03
(042E)
RUN
Terminal RP
Function Gain
Sets the gain used when the function in H6-01 [Terminal RP Pulse
Train Function] is input to terminal RP.
100.0%
(0.0 - 1000.0%)
932
H6-04
(042F)
RUN
Terminal RP
Function Bias
Sets the bias used when the function in H6-01 [Terminal RP Pulse
Train Function] is input to terminal RP. Sets a value when the pulse
train is 0 Hz.
0.0%
(-100.0 - 100.0%)
933
H6-05
(0430)
RUN
Terminal RP Filter
Time
Sets the time constant for the primary delay filters of the pulse train
input.
0.10 s
(0.00 - 2.00 s)
933
H6-06
(0431)
RUN
Terminal MP
Monitor Selection
Sets a function for pulse train monitor output terminal MP. Sets the
“x-xx” part of the Ux-xx monitor.
102
(000, 031, 101,
102, 105, 116, 501,
502, 801 - 809, 821
- 825, 831 - 839,
851 - 855)
933
H6-07
(0432)
RUN
Terminal MP
Frequency Scaling
Sets the frequency of the pulse train output signal used when the
monitor set with H6-06 [Terminal MP Monitor Selection] is 100%.
1440 Hz
(0 - 32000 Hz)
934
H6-08
(043F)
Terminal RP
Minimum
Frequency
Sets the minimum frequency of the pulse train signal that terminal
RP can detect.
0.5 Hz
(0.1 - 1000.0 Hz)
934
H6-09
(156E)
Voltage Phase Sync
MP Selection
Set whether to output the pulse synchronized with drive output
voltage phase from the pulse train monitor output terminal MP. This
parameter is only enabled when H6-06 = 102 [Terminal MP
Monitor Selection = Output Frequency] and H6-07 = 0 [Terminal
MP Frequency Scaling = 0 Hz].
0 : Disabled
1 : Enabled
0
(0, 1)
934
◆ H7: Virtual Inputs/Outputs
No.
(Hex.)
Name Description
Default
(Range)
Ref.
H7-00
(116F)
Expert
Virtual MFIO
selection
Sets the function to enable and disable the virtual I/O function. Set
this parameter to 1 to operate the virtual I/O function.
0 : Disabled
1 : Enabled
0
(0, 1)
935
H7-01
(1185)
Expert
Virtual Multi-
Function Input 1
Sets the function that enters the virtual input set in H7-10 [Virtual
Multi-Function Output 1].
F
(0 - 19F)
935
H7-02
(1186)
Expert
Virtual Multi-
Function Input 2
Sets the function that enters the virtual input set in H7-12 [Virtual
Multi-Function Output 2].
F
(0 - 19F)
935