Parameter Details
11
11.8 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 935
Figure 11.121 Virtual Analog I/O Functional Block Diagram
Figure 11.122 Virtual Digital I/O Functional Block Diagram
Note:
• Refer to H1-xx "MFDI Setting Values" for more information on the virtual digital input setting values.
• Refer to H2-xx "MFDO Setting Values" for more information on the virtual digital output setting values.
• Refer to H3-xx "MFAI Setting Values" for more information on the virtual analog input setting values.
• Refer to H4-xx "MFAO Setting Values" for more information on the virtual analog output setting values.
• 0 [3-Wire Sequence] and 20 to 2F [External Fault] cannot be selected in H7-01 to H7-04 [Virtual Multi-Function Input 1 to 4].
• If the terminal is not used, set H7-01 to H7-04 = F. However, the through mode function is not supported.
• The virtual I/O function selection and the multi-function input for DI-A3 cannot be used simultaneously.
■ H7-00: Virtual MFIO selection
No.
(Hex.)
Name Description
Default
(Range)
H7-00
(116F)
Expert
Virtual MFIO
selection
Sets the function to enable and disable the virtual I/O function. Set this
parameter to 1 to operate the virtual I/O function.
0
(0, 1)
0 : Disabled
1 : Enabled
■ H7-01: Virtual Multi-Function Input 1
No.
(Hex.)
Name Description
Default
(Range)
H7-01
(1185)
Expert
Virtual Multi-
Function Input 1
Sets the function that enters the virtual input set in H7-10 [Virtual Multi-
Function Output 1].
F
(0 - 19F)
■ H7-02: Virtual Multi-Function Input 2
No.
(Hex.)
Name Description
Default
(Range)
H7-02
(1186)
Expert
Virtual Multi-
Function Input 2
Sets the function that enters the virtual input set in H7-12 [Virtual Multi-
Function Output 2].
F
(0 - 19F)
■ H7-03: Virtual Multi-Function Input 3
No.
(Hex.)
Name Description
Default
(Range)
H7-03
(1187)
Expert
Virtual Multi-
Function Input 3
Sets the function that enters the virtual input set in H7-14 [Virtual Multi-
Function Output 3].
F
(0 - 19F)