Parameter Details
11
11.11 o: Keypad-Related Settings
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 1023
Note:
When you replace the LCD keypad then energize the drive, the keypad shows the restore operation screen automatically to restore the
drive configuration with the parameters backed up to the LCD keypad. If you connect an LCD keypad that does not have parameter
backup data, the keypad will not show the restore operation screen.
■ o3-07: Auto Parameter Backup Interval
No.
(Hex.)
Name Description
Default
(Range)
o3-07
(0BDF)
Auto Parameter
Backup Interval
Sets the interval at which the automatic parameter backup function saves
parameters from the drive to the keypad.
1
(0 - 3)
The drive saves parameter settings to the keypad at these times:
1. After you energize the drive and the auto backup period passes.
2. When you use ROM enter or the keypad to change parameters, the drive saves those changes in the drive,
waits for the auto backup period to pass, then saves those parameters in the keypad.
NOTICE: Think about this limit when you set the auto backup period. You can write data to the keypad a maximum of 100,000
times. If you write data to the keypad more than 100,000 times, it can cause data access errors and keypad failure.
0 : Every 10 minutes
1 : Every 30 minutes
2 : Every 60 minutes
3 : Every 12 hours
◆ o4: Maintenance Mon Settings
o4 parameters set the expected service life to help you know when to replace parts. The drive will show an alarm
to tell you when the replacement part interval is near.
■ o4-01: Elapsed Operating Time Setting
No.
(Hex.)
Name Description
Default
(Range)
o4-01
(050B)
Elapsed Operating
Time Setting
Sets the initial value of the cumulative drive operation time in 10-hour units.
0 h
(0 - 9999 h)
When you select o4-01 on the keypad, it will show the current value of U4-01 in units of 10 hours (h). When you
change the setting of o4-01 through the monitor, the U4-01 count starts again as specified by the setting of o4-01.
Note:
Set this parameter in 10-hour (h) units. When o4-01 = 30, U4-01 [Cumulative Ope Time] = 300 h.
■ o4-02: Elapsed Operating Time Selection
No.
(Hex.)
Name Description
Default
(Range)
o4-02
(050C)
Elapsed Operating
Time Selection
Sets the condition that counts the cumulative operation time.
0
(0, 1)
0 : U4-01 Shows Total Power-up Time
Counts the time from when the drive is energized to when it is de-energized.
1 : U4-01 Shows Total RUN Time
Counts the time that the drive outputs voltage.
■ o4-03: Fan Operation Time Setting
No.
(Hex.)
Name Description
Default
(Range)
o4-03
(050E)
Fan Operation Time
Setting
Sets the value from which to start the cumulative drive cooling fan
operation time in 10-hour units.
0 h
(0 - 9999 h)