10.5 b: Application
506 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
No.
(Hex.)
Name Description
Default
(Range)
Ref.
b3-54
(3123)
Search Time
Sets the length of time that the drive will run Speed Search.
400 ms
(10 - 2000 ms)
721
b3-55
(3124)
Expert
Current Increment
Time
Sets the length of time that the drive will increase the current from
zero current to the setting value of b3-06 [Speed Estimation Current
Level 1].
10 ms
(10 - 2000 ms)
721
◆ b4: Timer Function
No.
(Hex.)
Name Description
Default
(Range)
Ref.
b4-01
(01A3)
Timer Function
ON-Delay Time
Sets the ON-delay time for the timer input.
0.0 s
(0.0 - 3000.0 s)
722
b4-02
(01A4)
Timer Function
OFF-Delay Time
Sets the OFF-delay time for the timer input.
0.0 s
(0.0 - 3000.0 s)
722
b4-03
(0B30)
Expert
Terminal M1-M2
ON-Delay Time
Sets the delay time to activate the contact after the function set in
H2-01 activates.
0 ms
(0 - 65000 ms)
722
b4-04
(0B31)
Expert
Terminal M1-M2
OFF-Delay Time
Sets the delay time to deactivate the contact after the function set in
H2-01 deactivates.
0 ms
(0 - 65000 ms)
722
b4-05
(0B32)
Expert
Terminal M3-M4
ON-Delay Time
Sets the delay time to activate the contact after the function set in
H2-02 activates.
0 ms
(0 - 65000 ms)
722
b4-06
(0B33)
Expert
Terminal M3-M4
OFF-Delay Time
Sets the delay time to deactivate the contact after the function set in
H2-02 deactivates.
0 ms
(0 - 65000 ms)
723
b4-07
(0B34)
Expert
Terminal M5-M6
ON-Delay Time
Sets the delay time to activate the contact after the function set in
H2-03 activates.
0 ms
(0 - 65000 ms)
723
b4-08
(0B35)
Expert
Terminal M5-M6
OFF-Delay Time
Sets the delay time to deactivate the contact after the function set in
H2-03 deactivates.
0 ms
(0 - 65000 ms)
723