Parameter Details
11
11.10 n: Special Adjustment
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 993
The best value of this parameter changes when the flux saturation characteristics of the motor change.
Gradually increase the value of n3-13 to 1.25 or 1.30 to increase the braking power of Overexcitation
Deceleration. If the gain is too much, the motor can have flux saturation and cause a large quantity of current to
flow. This can increase the deceleration time.
Decrease the setting value if flux saturation causes overcurrent. If you increase the setting value, the drive can
detect oC [Overcurrent], oL1 [Motor Overload], and oL2 [Drive Overload]. Decrease the value of n3-21 [HSB
Current Suppression Level] to prevent oC and oL.
Regular use of overexcitation deceleration or extended periods of overexcitation deceleration can increase
internal motor temperatures. Decrease the setting value in these conditions.
If ov [Overvoltage] occurs, increase the deceleration time.
n3-14: OEB High Frequency Injection
No.
(Hex.)
Name Description
Default
(Range)
n3-14
(0532)
Expert
OEB High Frequency
Injection
Sets the function that injects harmonic signals during overexcitation
deceleration.
0
(0, 1)
Enable this parameter to set a shorter deceleration time.
Note:
If you frequently use overexcitation deceleration on a motor, the motor loss will increase the risk of burn damage.
When you set this parameter to 1, the motor can make a loud excitation sound during overexcitation deceleration. If the excitation
sound is unwanted, set this parameter to 0 to disable the function.
0 : Disabled
1 : Enabled
The drive injects harmonic signals at the time of overexcitation deceleration. You can decrease the deceleration
time because motor loss increases.
n3-21: HSB Current Suppression Level
No.
(Hex.)
Name Description
Default
(Range)
n3-21
(0579)
HSB Current
Suppression Level
Sets the upper limit of the current that is suppressed at the time of
overexcitation deceleration, where the drive rated current = 100% value.
100%
(0 - 150%)
If flux saturation during Overexcitation Deceleration makes the motor current become more than the value set in
this parameter, the drive will automatically decrease the overexcitation gain. If oC [Overcurrent], oL1 [Motor
Overload], or oL2 [Drive Overloaded] occur during overexcitation deceleration, decrease the setting value.
If repetitive or long overexcitation deceleration cause the motor to overheat, decrease the setting value.
n3-23: Overexcitation Braking Operation
No.
(Hex.)
Name Description
Default
(Range)
n3-23
(057B)
Overexcitation
Braking Operation
Sets the direction of motor rotation where the drive will enable
overexcitation.
0
(0 - 2)
0 : Disabled
1 : Enabled Only when Rotating FWD
2 : Enabled Only when Rotating REV
Note:
When n3-23 = 1, 2, the drive enables overexcitation only in the direction of motor rotation in which a regenerative load is applied.
Increased motor loss can decrease ov [Overvoltage] faults.
n4: Adv Open Loop Vector Tune
The following explains how to make special adjustments for Advanced Open Loop Vector [A1-02 = 4].
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV