Parameter List
10
10.9 F: Options
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 531
10.9 F: Options
◆ F1: PG Option Setup (Encoder)
No.
(Hex.)
Name Description
Default
(Range)
Ref.
F1-01
(0380)
Encoder 1 Pulse
Count (PPR)
Sets the number of output pulses for each motor revolution.
1024 ppr
(1 - 60000 ppr)
821
F1-02
(0381)
Encoder Signal
Loss Detect Sel
Sets the method to stop the motor or let the motor continue
operating when the drive detects a PGo [Encoder (PG) Feedback
Loss].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : No Alarm Display
1
(0 - 4)
821
F1-03
(0382)
Overspeed
Detection Selection
Sets the method to stop the motor or let the motor continue
operating when the drive detects a oS [Overspeed].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : No Alarm Display
1
(0 - 3)
821
F1-04
(0383)
Speed Deviation
Detection Select
Sets the method to stop the motor or let the motor continue
operating when the drive detects a dEv [Speed Deviation].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
3
(0 - 3)
822
F1-05
(0384)
Encoder 1 Rotation
Selection
Sets the output sequence for the A and B pulses from the encoder,
assuming that the motor is operating in the forward direction.
0 : Pulse A leads in FWD Direction
1 : Pulse B leads in FWD Direction
Determined by A1-
02
(0, 1)
822
F1-06
(0385)
Encoder 1 Pulse
Monitor Scaling
Sets the ratio between the pulse input and the pulse output of the
encoder as a 3-digit number. The first digit is the numerator and the
second and third digits set the denominator.
The dividing ratio = (1 + x)/yz when the setting value is a 3-digit
value (xyz).
001
(001 - 032, 102 -
132 (1 - 1/32))
822
F1-08
(0387)
Overspeed
Detection Level
Sets the detection level of oS [Overspeed] as a percentage when the
maximum output frequency is 100%.
115%
(0 - 120%)
823
F1-09
(0388)
Overspeed
Detection Delay
Time
Sets the length of time that the speed feedback must be more than
the F1-08 level to cause an oS [Overspeed].
Determined by A1-
02
(0.0 - 2.0 s)
823
F1-10
(0389)
Speed Deviation
Detection Level
Sets the detection level of dEv [Speed Deviation] as a percentage
when the maximum output frequency is 100%.
10%
(0 - 50%)
823
F1-11
(038A)
Speed Deviation
Detect DelayTime
Sets the length of time that the difference between the frequency
reference and speed feedback must be more than the level in F1-10
to cause a dEv [Speed Deviation].
0.5 s
(0.0 - 10.0 s)
823
F1-12
(038B)
Encoder 1 Gear
Teeth 1
Sets the number of gear teeth on the motor side. This parameter and
F1-13 [Encoder 1 Gear Teeth 2] set the gear ratio between the
motor and encoder.
0
(0 - 1000)
823