Startup Procedure and
Test Run
3
3.8 Auto-Tuning
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 197
Table 3.12 Input Data for EZ Tuning
Input Data Parameters Unit
Auto-Tuning Mode
(T4-01 Value)
Motor Parameter
Setting
(0)
Line-to-Line
Resistance
(1)
Motor Type Selection T4-02 - x -
Motor Max Revolutions T4-03 min
-1
x -
Motor Rated Revolutions T4-04 min
-1
x -
Motor Rated Frequency T4-05 Hz x -
Motor Rated Voltage T4-06 V x -
Motor Rated Current T4-07 A x x
Motor Rated Capacity T4-08 kW x -
Number of Poles T4-09 - x -
◆ Control Tuning
To increase drive responsiveness and prevent hunting, use Auto-Tuning to automatically adjust the control-related
parameters.
These types of Auto-Tuning are available for the control system:
• Inertia Tuning
• ASR Tuning
• Deceleration Rate Tuning
• KEB Tuning
Note:
If you do Control Tuning, you cannot set H1-xx = 16 [Motor 2 Selection]. Do not do Control Tuning for applications that switch
between motor 1 and motor 2.
Table 3.13 Control Loop Tuning Selection
Mode T3-00
Application Conditions
and Benefits
Applicable Control Method (A1-02 Value)
V/f
(0)
CL-V/f
(1)
OLV
(2)
CLV
(3)
AOLV
(4)
OLV/
PM
(5)
AOLV/
PM
(6)
CLV/
PM
(7)
EZOL
V
(8)
Inertia
Tuning
0
• For Feed Forward Control
• When L2-29 = 1 [Kinetic
Energy Backup Method =
Single Drive KEB Ride-
Thru 2].
• When MFDI H1-xx = 7A
[KEB Ride-Thru 2 Activate
(N.C.)].
- - - x - - - x -
ASR Tuning 1
To let the set response
frequency (including Inertia
Tuning) automatically adjust
the ASR gain.
- - - x - - - x -
Deceleration
Rate Tuning
2
To automatically adjust the
deceleration rate to prevent an
ov [Overvoltage] fault.
x x x x x x x x x
KEB Tuning 3
• To automatically adjust
parameter settings to
prevent an ov
[Overvoltage] fault with the
KEB Ride-Thru function.
• When L3-11 = 1
[Overvoltage Suppression
Select = Enabled].
x x x x x x x x x