Parameter List
10
10.13 o: Keypad-Related Settings
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 591
No.
(Hex.)
Name Description
Default
(Range)
Ref.
o4-12
(0512)
kWh Monitor
Initialization
Resets the monitor values for U4-10 [kWh, Lower 4 Digits] and U4-
11 [kWh, Upper 5 Digits].
0 : No Reset
1 : Reset
0
(0, 1)
1025
o4-13
(0528)
RUN Command
Counter @
Initialize
Resets the monitor values for U4-02 [Num of Run Commands], U4-
24 [Number of Runs (Low)], and U4-25 [Number of Runs(High)].
0 : No Reset
1 : Reset
0
(0, 1)
1025
o4-22
(154F)
RUN
Time Format
Sets the time display format. This parameter is only available when
using an LCD keypad.
0 : 24 Hour Clock
1 : 12 Hour Clock
2 : 12 Hour JP Clock
0
(0 - 2)
1025
o4-23
(1550)
RUN
Date Format
Sets the date display format. This parameter is only available when
using an LED keypad.
0 : YYYY/MM/DD
1 : DD/MM/YYYY
2 : MM/DD/YYYY
0
(0 - 2)
1025
o4-24
(310F)
RUN
bAT Detection
Selection
Sets operation when the drive detects bAT [Keypad Battery Low
Voltage] and TiM [Keypad Time Not Set].
0 : Disable
1 : Enable (Alarm Detected)
2 : Enable (Fault Detected)
0
(0 - 2)
1026
◆ o5: Log Function
No.
(Hex.)
Name Description
Default
(Range)
Ref.
o5-01
(1551)
RUN
Log Start/Stop
Selection
Sets the data log function. This parameter is only available on an
LCD keypad.
0 : OFF
1 : ON
0
(0 - 1)
1029
o5-02
(1552)
RUN
Log Sampling
Interval
Sets the data log sampling cycle. This parameter is only available on
an LCD keypad.
1000 ms
(100 - 6000 ms)
1029
o5-03
(1553)
RUN
Log Monitor Data
1
Sets the data log monitor. This parameter is only available on an
LCD keypad.
101
(000,101 - 855)
1029
o5-04
(1554)
RUN
Log Monitor Data
2
Sets the data log monitor. This parameter is only available on an
LCD keypad.
102
(000,101 - 855)
1029
o5-05
(1555)
RUN
Log Monitor Data
3
Sets the data log monitor. This parameter is only available on an
LCD keypad.
103
(000,101 - 855)
1030
o5-06
(1556)
RUN
Log Monitor Data
4
Sets the data log monitor. This parameter is only available on an
LCD keypad.
107
(000,101 - 855)
1030
o5-07
(1557)
RUN
Log Monitor Data
5
Sets the data log monitor. This parameter is only available on an
LCD keypad.
108
(000,101 - 855)
1030