Parameter Details
11
11.11 o: Keypad-Related Settings
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 1029
No. Item
Number of
Charac
ters
Description
15 Encoding data 4 Encoding data for log monitor data 1 through 10 (Hex.)
Bits 0 through 9 show the encoding of log monitor data 1 1 through 10. A bit value of 1
shows that the data represents a negative value. (Log monitor data 1 through 10 is absolute
value data without encoding)
Example when log monitor data 2, 5, and 8 show negative values: Bits 1, 4, and 7 have
values of 1, and the encoding data = 0010010010 (Bin.) = 0092 (Hex.)
16 Row number 6 Row number (Hex.) in the data log file
■ o5-01: Log Start/Stop Selection
No.
(Hex.)
Name Description
Default
(Range)
o5-01
(1551)
RUN
Log Start/Stop
Selection
Sets the data log function. This parameter is only available on an LCD
keypad.
0
(0 - 1)
0 : OFF
Stops the data log.
1 : ON
Starts the data log as specified by the sampling cycle set in o5-02 [Log Sampling Interval].
■ o5-02: Log Sampling Interval
No.
(Hex.)
Name Description
Default
(Range)
o5-02
(1552)
RUN
Log Sampling
Interval
Sets the data log sampling cycle. This parameter is only available on an
LCD keypad.
1000 ms
(100 - 6000 ms)
■ o5-03: Log Monitor Data 1
No.
(Hex.)
Name Description
Default
(Range)
o5-03
(1553)
RUN
Log Monitor Data 1
Sets the data log monitor. This parameter is only available on an LCD
keypad.
101
(000,101 - 855)
Note:
Set the log data with values 101 to 999 [U1-01 to U9-99].
For example, to show U1-05 [Motor Speed], set o5-03 = 105. When it is not necessary to set data log monitors, set this parameter to
000. You cannot set U2 monitors [Fault Trace] or U3 Monitors [Fault History].
■ o5-04: Log Monitor Data 2
No.
(Hex.)
Name Description
Default
(Range)
o5-04
(1554)
RUN
Log Monitor Data 2
Sets the data log monitor. This parameter is only available on an LCD
keypad.
102
(000,101 - 855)
Note:
Set the log data with values 101 to 999 [U1-01 to U9-99].
For example, to show U1-05 [Motor Speed], set o5-04 = 105. When it is not necessary to set data log monitors, set this parameter to
000. You cannot set U2 monitors [Fault Trace] or U3 Monitors [Fault History].