9.3 Model Specifications (200 V Class)
446 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
9.3 Model Specifications (200 V Class)
Table 9.2 Rating (200 V Class)
Model 2004 2006 2010 2012 2018 2021 2030 2042
Maximum Applicable
Motor Output (kW)
HD1
*1
0.55 0.75 1.5 2.2 3 4 5.5 7.5
ND1
*2
0.75 1.1 2.2 3 4 5.5 7.5 11
Maximum Applicable
Motor Output (HP)
HD1
*1
1/2 1 2 3 4 5 7 1/2 10
ND1
*2
3/4 1 1/2 3 4 5 7 1/2 10 15
Input
Rated
Input
Current
*3
(A)
HD1 (AC) 3.6 4.8 8.9 12.7 17 20.7 30 40.3
HD1 (DC) 4.5 5.9 11 16 21 25 37 49
ND1 (AC) 4.8 6.7 12.7 17 20.7 30 40.3 52
ND1 (DC) 5.9 8.2 16 21 25 37 49 71
Outputs
Rated
Output
Capacity
(kVA)
HD1
*4
1.2 1.9 3.0 4.2 5.3 6.7 9.5 12.6
ND1
*5
1.3 2.3 3.7 4.6 6.7 8.0 11.4 16.0
Rated
Output
Current
(A)
HD1 3.2 5 8 11 14 17.5 25 33
ND1 3.5 6 9.6 12.2 17.5 21 30 42
Overload Tolerance
• HD: 150% of the rated output current for 60 seconds
• ND: 110% of the rated output current for 60 seconds
Note:
Derating may be necessary for applications that start and stop frequently.
Carrier Frequency
HD1: 8 kHz without derating the drive capacity.
ND1: 2 kHz without derating the drive capacity.
Derate the drive capacity to use values to 15 kHz maximum.
Maximum Output
Voltage
Three-phase 200 V to 240 V
Note:
The maximum output voltage is proportional to the input voltage.
Maximum Output
Frequency
• Advanced Open Loop Vector Control (AOLV) and EZ Open Loop Vector Control (EZOLV): 120
Hz
• Closed Loop V/f Control (CL-V/f), Closed Loop Vector Control (CLV), Advanced Open Loop
Vector Control for PM (AOLV/PM), and Closed Loop Vector Control for PM (CLV/PM): 400 Hz
• V/f Control (V/f), Open Loop Vector Control (OLV), and Open Loop Vector Control for PM
(OLV/PM): 590 Hz
Measures
for
Harmonics
DC Reactor External options
Braking
Device
Braking Transistor Standard internal characteristics
EMC
Filter
EMC Filter
IEC61800-3, C2/C3
Factory option
• Models 2xxxB: There is a category C3 EMC filter in the drive.
• Models 2xxxC: There is a category C2 EMC filter in the drive.
Power
Supply
Rated Voltage/Rated
Frequency
• Three-phase AC power supply 200 V to 240 V at 50/60 Hz
• DC power supply 270 V to 340 V
Permitted Voltage
Fluctuation
-15% to +10%
Permitted Frequency
Fluctuation
±5%
Input
Power
(kVA)
HD1 1.5 2.0 3.7 5.3 7.1 8.6 12.5 16.8
ND1 2.0 2.8 5.3 7.1 8.6 12.5 16.8 21.6
*1 The maximum applicable motor output complies with 208 V motor ratings as specified in NEC Table 430.250. The rated output
current of the drive output amps must be equal to or more than the motor rated current.
*2 The maximum applicable motor output is based on 4-pole, general-purpose 220 V motor ratings. The rated output current of the drive
output amps must be equal to or more than the motor rated current.