10.10 H: Terminal Functions
560 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Setting Function Description Ref.
66 Comparator1
The monitor value set with H2-20 [Comparator 1 Monitor Selection] is on while in range
of the time set with H2-24 [Comparator 1 On-Delay Time] and the values of H2-21
[Comparator 1 Lower Limit] and H2-22 [Comparator 1 Upper Limit] are in range.
909
67 Comparator2
The monitor value set with H2-26 [Comparator 2 Monitor Selection] is on while in range
of the time set with H2-30 [Comparator 2 On-Delay Time] and the values of H2-27
[Comparator 2 Lower Limit] and H2-28 [Comparator 2 Upper Limit] are in range.
910
69 External Power
24V Supply
The terminal activates when there is an external 24V power supply between terminals
PS-AC.
ON : An external 24V power supply supplies power.
OFF : An external 24V power supply does not supply power.
910
6A Data Logger Error
The terminal activates when the drive detects a LoG [Com Error / Abnormal SD card].
910
90 to 93 DWEZ Digital
Outputs 1 to 4
Sets the DriveWorksEZ digital output. Refer to the DriveWorksEZ online manual for
more information.
911
A0 to A7 DWEZ Extended
Digital Output 1 to
8
Sets the digital output for the DriveWorksEZ DO-A3 option card. Refer to the
DriveWorksEZ online manual for more information.
911
100 to 1A7 Inverse Output of 0
to A7
Causes inverse output of the function for the selected MFDO. Uses the last two digits of
1xx to select which function to inversely output.
911
◆ H3: Analog Inputs
No.
(Hex.)
Name Description
Default
(Range)
Ref.
H3-01
(0410)
Terminal A1 Signal
Level Select
Sets the input signal level for MFAI terminal A1.
0 : 0 to 10V (Lower Limit at 0)
1 : -10 to +10V (Bipolar Reference)
2 : 4 to 20 mA
3 : 0 to 20 mA
0
(0 - 3)
913
H3-02
(0434)
Terminal A1
Function Selection
Sets a function for MFAI terminal A1.
0
(0 - 32)
913
H3-03
(0411)
RUN
Terminal A1 Gain
Setting
Sets the gain of the analog signal input to MFAI terminal A1.
100.0%
(-999.9 - +999.9%)
913
H3-04
(0412)
RUN
Terminal A1 Bias
Setting
Sets the bias of the analog signal input to MFAI terminal A1.
0.0%
(-999.9 - +999.9%)
914
H3-05
(0413)
Terminal A3 Signal
Level Select
Sets the input signal level for MFAI terminal A3.
0 : 0-10V (LowLim=0)
1 : -10 to +10V (Bipolar Reference)
2 : 4 to 20 mA
3 : 0 to 20 mA
0
(0 - 3)
914
H3-06
(0414)
Terminal A3
Function Selection
Sets a function for MFAI terminal A3.
2
(0 - 32)
914
H3-07
(0415)
RUN
Terminal A3 Gain
Setting
Sets the gain of the analog signal input to MFAI terminal A3.
100.0%
(-999.9 - +999.9%)
915
H3-08
(0416)
RUN
Terminal A3 Bias
Setting
Sets the bias of the analog signal input to MFAI terminal A3.
0.0%
(-999.9 - +999.9%)
915