4.3 UL Standards
276 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Drive Model
Maximum Applicable
Motor Output
kW (HP)
Input Voltage < 460 V
Maximum Applicable
Motor Output
kW (HP)
Input Voltage 460 V
Input Current Rating
A
Semiconductor
Protection Fuse Rated
Current
Manufacturer: EATON/
Bussmann
4568 250 (335) 300 (400) 465 FWH-1200A
4675 315 (400) 335 (450) 584
FWH-1400A
FWH-1600A
*1
*1 Yaskawa recommends a fuse with a large rated current for applications with repeated loads.
Low Voltage Wiring for Control Circuit Terminals
You must provide low voltage wiring as specified by the National Electric Code (NEC), the Canadian Electric
Code, Part I (CEC), and local codes. Yaskawa recommends the NEC class 1 circuit conductor. Use the UL
approved class 2 power supply for external power supply.
Table 4.18 Control Circuit Terminal Power Supplies
Input/Output Terminals Power Supply Specifications
Digital input S1 to S8, SN, SC, SP
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for
external power supply.
Analog input A1 to A3, AC, +V, -V
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for
external power supply.
Analog output FM, AM, AC Uses the LVLC power supply in the drive.
Pulse train output MP, AC
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for
external power supply.
Pulse train input RP, AC
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for
external power supply.
Safe disable input H1, H2, HC
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for
external power supply.
Serial communication input/output D+, D-, AC
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for
external power supply.
24 V external power supply PS, AC Use the UL Listed class 2 power supply.
Drive Motor Overload and Overheat Protection
The drive motor overload and overheat protection function complies with the National Electric Code (NEC) and
the Canadian Electric Code, Part I (CEC).
Set the Motor Rated Current and L1-01 through L1-04 [Motor Overload Protection Select] correctly to enable
motor overload and overheat protection.
Refer to the control method and set the motor rated current with E2-01 [Motor Rated Current (FLA)], E5-03 [PM
Motor Rated Current (FLA)], or E9-06 [Motor Rated Current (FLA)].
E2-01: Motor Rated Current (FLA)
No.
(Hex.)
Name Description
Default
(Range)
E2-01
(030E)
Motor Rated Current
(FLA)
Sets the motor rated current in amps.
Determined by o2-04
and C6-01
(10% to 200% of the
drive rated current)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV