10.5 b: Application
510 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
No.
(Hex.)
Name Description
Default
(Range)
Ref.
b5-67
(11DF)
PID Differential
FB Monitor Lvl
Sets the signal level for the monitor specified in b5-63 [PID
Differential FB Monitor Sel].
0 : Absolute
1 : Bi-directional (+/-)
0
(0, 1)
738
b5-89
(0B89)
RUN
Sleep Method
Selection
Sets sleep and wake up operation when using PID.
0 : Standard
1 : EZ Sleep/Wake-up
0
(0, 1)
738
b5-90
(0B90)
EZ Sleep Unit
Sets the measurement units for b5-91 [EZ Sleep Minimum Speed]
and b5-92 [EZ Sleep Level].
0 : 0.1Hz units
1 : rev/min
0
(0, 1)
739
b5-91
(0B91)
RUN
EZ Sleep
Minimum Speed
Sets the minimum speed for the EZ Sleep/Wakeup function. This
parameter uses the largest value from b5-91, b5-34 [PID Output
Lower Limit Level], and d2-02 [Frequency Reference Lower Limit].
0.0 Hz or 0 min
-1
(r/min)
(0.0 to 590.0 Hz or
0 to 35400 min
-1
(r/
min))
739
b5-92
(0B92)
RUN
EZ Sleep Level
Sets the value that the output frequency or motor speed must be less
than for longer than b5-93 [EZ Sleep Time] to enter Sleep Mode.
0.0 Hz or 0 min
-1
(r/min)
(0.0 to 590.0 Hz or
0 to 35400 min
-1
(r/
min))
739
b5-93
(0B93)
RUN
EZ Sleep Time
Sets the length of time that the output frequency or motor speed
must be less than b5-92 [EZ Sleep Level] to enter Sleep Mode.
5.0 s
(0.0 - 1000.0 s)
739
b5-94
(0B94)
RUN
EZ Sleep Wake-up
Level
Sets the level at which the drive resumes operation when exiting
Sleep Mode.
0.00%
(0.00 - 600.00%)
739
b5-95
(0B95)
EZ Sleep Wake-up
Mode
Sets the wake-up mode to use when exiting Sleep Mode.
0 : Absolute
1 : Setpoint Delta
0
(0, 1)
740
b5-96
(0B96)
EZ Sleep Wake-up
Time
Sets the EZ Wake-up time.
1.0 s
(0.0 - 1000.0 s)
740
◆ b6: Dwell Function
No.
(Hex.)
Name Description
Default
(Range)
Ref.
b6-01
(01B6)
Dwell Reference at
Start
Sets the output frequency that the drive will hold momentarily when
the motor starts.
0.0
(Determined by
A1-02)
740
b6-02
(01B7)
Dwell Time at Start
Sets the length of time that the drive will hold the output frequency
when the motor starts.
0.0 s
(0.0 - 10.0 s)
741
b6-03
(01B8)
Dwell Reference at
Stop
Sets the output frequency that the drive will hold momentarily when
ramping to stop the motor.
0.0
(Determined by
A1-02)
741
b6-04
(01B9)
Dwell Time at Stop
Sets the length of time for the drive to hold the output frequency
when ramping to stop the motor.
0.0 s
(0.0 - 10.0 s)
741