Parameter List
10
10.5 b: Application
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 509
No.
(Hex.)
Name Description
Default
(Range)
Ref.
b5-39
(01FF)
PID User Unit
Display Digits
Sets the number of digits to set and show the PID setpoint.
0 : No Decimal Places (XXXXX)
1 : One Decimal Places (XXXX.X)
2 : Two Decimal Places (XXX.XX)
3 : Three Decimal Places (XX.XXX)
Determined by b5-
20
(0 - 3)
735
b5-40
(017F)
Frequency
Reference Monitor
@PID
Sets the contents for monitor U1-01 [Frequency Reference] in PID
control.
0 : U1-01 Includes PID Output
1 : U1-01 Excludes PID Output
0
(0, 1)
735
b5-47
(017D)
PID Trim Mode
Output Reverse Sel
Sets reverse motor rotation when the PID control output is negative.
0 : Lower Limit is Zero
1 : Negative Output Accepted
1
(0, 1)
735
b5-53
(0B8F)
RUN
PID Integrator
Ramp Limit
Sets the responsiveness of PID control when the PID feedback
changes quickly.
0.0 Hz
(0.0 - 10.0 Hz)
736
b5-54
(0BB7)
PID Softstarter
Cancel Selection
Sets how the soft-starter responds to PID input/output.
0 : Disabled
1 : Enabled
0
(0, 1)
736
b5-55
(0BE1)
PID Feedback
Monitor Selection
Sets the monitor for PID Feedback (Ux-xx).
000
(000 - 999)
736
b5-56
(0BE2)
PID Feedback
Monitor Gain
Sets the gain for the monitor specified in b5-55 [PID Feedback
Monitor Selection].
1.00
(0.00 - 10.00)
736
b5-57
(11DD)
PID Feedback
Monitor Bias
Sets the bias for the monitor specified in b5-55 [PID Feedback
Monitor Selection].
0.00
(-10.00 - +10.00)
737
b5-58 to b5-
60
(1182 -
1184)
RUN
PID Setpoints 2 to
4
Sets the PID setpoint when H1-xx = 3E or 3F [MFDI Function
Select = PID Setpoint Selection 1/2]. This value is a percentage
where E1-04 [Maximum Output Frequency] setting = a setting value
of 100%.
0.00%
(0.00 - 100.00%)
737
b5-61
(119A)
PID Trim Mode
Lower Limit Sel
Sets the function that adjusts the PID output in relation to the
frequency reference.
0 : Disabled
1 : Enabled
0
(0, 1)
737
b5-62
(119B)
PID Trim Mode
Lower Limit Value
Sets the lower limit of the PID frequency reference trim as a
percentage where E1-04 [Maximum Output Frequency] setting = a
setting value of 100%.
0.00%
(0.00 - 100.00%)
737
b5-63
(119C)
PID Differential
FB Monitor Sel
Sets the monitor for PID Differential Feedback (Ux-xx).
000
(000 - 999)
738
b5-64
(119D)
PID Differential
FB Monitor Gain
Sets the gain for the monitor specified in b5-63 [PID Differential
FB Monitor Sel].
1.00
(0.00 - 10.00)
738
b5-65
(119F)
PID Differential
FB Monitor Bias
Sets the bias for the monitor specified in b5-63 [PID Differential FB
Monitor Sel].
0.00
(-10.00 - +10.00)
738
b5-66
(11DE)
PID Feedback
Monitor Level
Sets the signal level for the monitor specified in b5-55 [PID
Feedback Monitor Selection].
0 : Absolute
1 : Bi-directional (+/-)
0
(0, 1)
738