11.3 b: Application
738 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
■ b5-63: PID Differential FB Monitor Sel
No.
(Hex.)
Name Description
Default
(Range)
b5-63
(119C)
PID Differential FB
Monitor Sel
Sets the monitor for PID Differential Feedback (Ux-xx).
000
(000 - 999)
Note:
• You cannot select parameter U5-xx.
• This parameter is disabled when set to 000.
■ b5-64: PID Differential FB Monitor Gain
No.
(Hex.)
Name Description
Default
(Range)
b5-64
(119D)
PID Differential FB
Monitor Gain
Sets the gain for the monitor specified in b5-63 [PID Differential FB
Monitor Sel].
1.00
(0.00 - 10.00)
Note:
Set b5-18 = 1 [b5-19 PID Setpoint Selection = Enabled] to enable this parameter.
■ b5-65: PID Differential FB Monitor Bias
No.
(Hex.)
Name Description
Default
(Range)
b5-65
(119F)
PID Differential FB
Monitor Bias
Sets the bias for the monitor specified in b5-63 [PID Differential FB
Monitor Sel].
0.00
(-10.00 - +10.00)
Note:
Set b5-18 = 1 [b5-19 PID Setpoint Selection = Enabled] to enable this parameter.
■ b5-66: PID Feedback Monitor Level
No.
(Hex.)
Name Description
Default
(Range)
b5-66
(11DE)
PID Feedback
Monitor Level
Sets the signal level for the monitor specified in b5-55 [PID Feedback
Monitor Selection].
0
(0, 1)
0 : Absolute
1 : Bi-directional (+/-)
■ b5-67: PID Differential FB Monitor Lvl
No.
(Hex.)
Name Description
Default
(Range)
b5-67
(11DF)
PID Differential FB
Monitor Lvl
Sets the signal level for the monitor specified in b5-63 [PID Differential FB
Monitor Sel].
0
(0, 1)
0 : Absolute
1 : Bi-directional (+/-)
■ b5-89: Sleep Method Selection
No.
(Hex.)
Name Description
Default
(Range)
b5-89
(0B89)
RUN
Sleep Method
Selection
Sets sleep and wake up operation when using PID.
0
(0, 1)
0 : Standard
1 : EZ Sleep/Wake-up