Parameter List
10
10.17 U: Monitors
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 599
10.17 U: Monitors
◆ U1: Operation Status Monitors
No.
(Hex.)
Name Description
MFAO Signal
Level
Ref.
U1-01
(0040)
Frequency
Reference
Shows the actual frequency reference value. Parameter o1-03
[Frequency Display Unit Selection] selects the units.
Unit: 0.01 Hz
10 V = Max.
frequency (-10 V
to +10 V)
-
U1-02
(0041)
Output Frequency
Shows the actual output frequency. Parameter o1-03 [Frequency
Display Unit Selection] selects the units.
Unit: 0.01 Hz
10 V = Max.
frequency (-10 V
to +10 V)
-
U1-03
(0042)
Output Current
Shows the actual output current.
The keypad shows the value of U1-03 in amperes (A). When
looking at the monitor through MEMOBUS/Modbus
communications, the current is “8192 = drive rated current (A).”
Calculate the current from the monitor value that is in at
MEMOBUS/Modbus communications using “Numerals being
displayed / 8192 × drive rated current (A).”
Unit: Determined by the drive model.
• 0.01 A: 2004 to 2042, 4002 to 4023
• 0.1 A: 2056 to 2415, 4031 to 4675
10 V = Drive rated
current
-
U1-04
(0043)
Control Method
Shows the drive control method.
0 : V/f Control
1 : V/f Control with Encoder
2 : Open Loop Vector
3 : Closed Loop Vector
4 : Advanced Open Loop Vector
5 : PM Open Loop Vector
6 : PM Advanced Open Loop Vector
7 : PM Closed Loop Vector
8 : EZ Vector Control
No signal output
available
-
U1-05
(0044)
Motor Speed
Shows the actual detected motor speed. Parameter o1-03
[Frequency Display Unit Selection] selects the units.
Unit: 0.01 Hz
10 V = Max.
frequency (-10 V
to +10 V)
-
U1-06
(0045)
Output Voltage Ref
Shows the output voltage reference.
Unit: 0.1 V
200 V class: 10 V
= 200 Vrms
400 V class: 10 V
= 400 Vrms
-
U1-07
(0046)
DC Bus Voltage
Shows the DC bus voltage.
Unit: 1 V
200 V class: 10 V
= 200 V
400 V class: 10 V
= 400 V
-
U1-08
(0047)
Output Power
Shows the internally-calculated output power.
Changing the setting of A1-02 [Control Method Selection] also
changes the signal level of the analog output.
• A1-02 = 0, 1 [V/f Control]: Drive capacity (kW)
• A1-02 = 2 to 8 [Vector Control]: Motor Rated Power (kW) [E2-
11]
Unit: Drive capacity and C6-01 [Normal / Heavy Duty Selection]
calculate the maximum applicable motor output.
• Less than 11 kW (15 HP): 0.01 kW
• Less than 11 kW (15 HP): 0.1 kW
10 V: Drive
capacity (motor
rated power) kW
(-10 V to +10 V)
-