11.3 b: Application
722 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Figure 11.33 Example of Timer Function Operation
Setting on/off-delay time for MFDO
Figure 11.34 uses H2-01 terminals to show an example of how the timer function works. Use b4-03 [Terminal
M1-M2 ON-Delay Time] and b4-04 [Terminal M1-M2 OFF-Delay Time] to set this function.
Figure 11.34 Example of How the Timer Function Works with H2-01 Terminals
Note:
When the terminal is triggered, it continues for a minimum of 100 ms. The on/off-delay time of MFDO terminal does not have an effect.
b4-01: Timer Function ON-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
b4-01
(01A3)
Timer Function ON-
Delay Time
Sets the ON-delay time for the timer input.
0.0 s
(0.0 - 3000.0 s)
b4-02: Timer Function OFF-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
b4-02
(01A4)
Timer Function OFF-
Delay Time
Sets the OFF-delay time for the timer input.
0.0 s
(0.0 - 3000.0 s)
b4-03: Terminal M1-M2 ON-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
b4-03
(0B30)
Expert
Terminal M1-M2
ON-Delay Time
Sets the delay time to activate the contact after the function set in H2-01
activates.
0 ms
(0 - 65000 ms)
b4-04: Terminal M1-M2 OFF-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
b4-04
(0B31)
Expert
Terminal M1-M2
OFF-Delay Time
Sets the delay time to deactivate the contact after the function set in H2-01
deactivates.
0 ms
(0 - 65000 ms)
b4-05: Terminal M3-M4 ON-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
b4-05
(0B32)
Expert
Terminal M3-M4
ON-Delay Time
Sets the delay time to activate the contact after the function set in H2-02
activates.
0 ms
(0 - 65000 ms)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV