Parameter List
10
10.10 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 567
No.
(Hex.)
Name Description
Default
(Range)
Ref.
H7-03
(1187)
Expert
Virtual Multi-
Function Input 3
Sets the function that enters the virtual input set in H7-14 [Virtual
Multi-Function Output 3].
F
(0 - 19F)
935
H7-04
(1188)
Expert
Virtual Multi-
Function Input 4
Sets the function that enters the virtual input set in H7-16 [Virtual
Multi-Function Output 4].
F
(0 - 19F)
936
H7-10
(11A4)
Expert
Virtual Multi-
Function Output 1
Sets the function for virtual digital output 1.
F
(0 - 1A7)
936
H7-11
(11A5)
Expert
Virtual Output 1
Delay Time
Sets the minimum ON time for virtual digital output 1.
0.1 s
(0.0 - 25.0 s)
936
H7-12
(11A6)
Expert
Virtual Multi-
Function Output 2
Sets the function for virtual digital output 2.
F
(0 - 1A7)
936
H7-13
(11A7)
Expert
Virtual Output 2
Delay Time
Sets the minimum ON time for virtual digital output 2.
0.1 s
(0.0 - 25.0 s)
936
H7-14
(11A8)
Expert
Virtual Multi-
Function Output 3
Sets the function for virtual digital output 3.
F
(0 - 1A7)
936
H7-15
(11A9)
Expert
Virtual Output 3
Delay Time
Sets the minimum ON time for virtual digital output 3.
0.1 s
(0.0 - 25.0 s)
936
H7-16
(11AA)
Expert
Virtual Multi-
Function Output 4
Sets the function for virtual digital output 4.
F
(0 - 1A7)
937
H7-17
(11AB)
Expert
Virtual Output 4
Delay Time
Sets the minimum ON time for virtual digital output 4.
0.1 s
(0.0 - 25.0 s)
937
H7-30
(1177)
Virtual Analog
Input Selection
Sets the virtual analog input function.
F
(0 - 32)
937
H7-31
(1178)
RUN
Expert
Virtual Analog
Input Gain
Sets the virtual analog input gain.
100.0%
(-999.9 - 999.9%)
937
H7-32
(1179)
RUN
Expert
Virtual Analog
Input Bias
Sets the virtual analog input bias.
0.0%
(-999.9 - 999.9%)
937
H7-40
(1163)
Virtual Analog Out
Signal Select
Sets the signal level of the virtual analog output.
0 : 0 to 100% (Absolute Value)
1 : -100 to 100%
2 : 0 to 100% (Lower Limit at 0)
0
(0 - 2)
937
H7-41
(1164)
Virtual Analog
Output Function
Sets the monitor to be output from the virtual analog output. Set the
x-xx part of the Ux-xx [Monitor]. For example, set x-xx to 102 to
monitor U1-02 [Output Frequency].
102
(0 - 999)
937
H7-42
(1165)
Virtual Analog
Output FilterTime
Sets the time constant for a primary filter of the virtual analog
output.
0.00 s
(0.00 - 2.00 s)
938