Parameter Details
11
11.8 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 937
■ H7-16: Virtual Multi-Function Output 4
No.
(Hex.)
Name Description
Default
(Range)
H7-16
(11AA)
Expert
Virtual Multi-
Function Output 4
Sets the function for virtual digital output 4.
F
(0 - 1A7)
■ H7-17: Virtual Output 4 Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H7-17
(11AB)
Expert
Virtual Output 4
Delay Time
Sets the minimum ON time for virtual digital output 4.
0.1 s
(0.0 - 25.0 s)
■ H7-30: Virtual Analog Input Selection
No.
(Hex.)
Name Description
Default
(Range)
H7-30
(1177)
Virtual Analog Input
Selection
Sets the virtual analog input function.
F
(0 - 32)
■ H7-31: Virtual Analog Input Gain
No.
(Hex.)
Name Description
Default
(Range)
H7-31
(1178)
RUN
Expert
Virtual Analog Input
Gain
Sets the virtual analog input gain.
100.0%
(-999.9 - 999.9%)
■ H7-32: Virtual Analog Input Bias
No.
(Hex.)
Name Description
Default
(Range)
H7-32
(1179)
RUN
Expert
Virtual Analog Input
Bias
Sets the virtual analog input bias.
0.0%
(-999.9 - 999.9%)
■ H7-40: Virtual Analog Out Signal Select
No.
(Hex.)
Name Description
Default
(Range)
H7-40
(1163)
Virtual Analog Out
Signal Select
Sets the signal level of the virtual analog output.
0
(0 - 2)
0 : 0 to 100% (Absolute Value)
1 : -100 to 100%
2 : 0 to 100% (Lower Limit at 0)
■ H7-41: Virtual Analog Output Function
No.
(Hex.)
Name Description
Default
(Range)
H7-41
(1164)
Virtual Analog
Output Function
Sets the monitor to be output from the virtual analog output. Set the x-xx
part of the Ux-xx [Monitor]. For example, set x-xx to 102 to monitor U1-02
[Output Frequency].
102
(0 - 999)