Parameter Details
11
11.8 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 933
■ H6-04: Terminal RP Function Bias
No.
(Hex.)
Name Description
Default
(Range)
H6-04
(042F)
RUN
Terminal RP
Function Bias
Sets the bias used when the function in H6-01 [Terminal RP Pulse Train
Function] is input to terminal RP. Sets a value when the pulse train is 0 Hz.
0.0%
(-100.0 - 100.0%)
■ H6-05: Terminal RP Filter Time
No.
(Hex.)
Name Description
Default
(Range)
H6-05
(0430)
RUN
Terminal RP Filter
Time
Sets the time constant for the primary delay filters of the pulse train input.
0.10 s
(0.00 - 2.00 s)
■ H6-06: Terminal MP Monitor Selection
No.
(Hex.)
Name Description
Default
(Range)
H6-06
(0431)
RUN
Terminal MP Monitor
Selection
Sets a function for pulse train monitor output terminal MP. Sets the “x-xx”
part of the Ux-xx monitor.
102
(000, 031, 101, 102,
105, 116, 501, 502,
801 - 809, 821 - 825,
831 - 839, 851 - 855)
Note:
To use in through mode or when terminal MP is not used, set this parameter to 000 or 031.
When you use the pulse train monitor, make sure that you connect peripheral devices as specified by these load
conditions:
Incorrect connections can make the characteristics not sufficient or cause mechanical damage.
• Use the pulse train monitor as the sourcing output.
Output Voltage
VRL(V)
Load Impedance (kΩ)
5 Vor more 1.5 kΩ or more
8 Vor more 4.0 kΩ or more
10 Vor more 10 kΩ or more
Figure 11.119 Circuit Diagram When Used as the Sourcing Output
• Use the pulse train monitor as the sinking input
External Power Supply (V) 12 VDC ± 10%, 15 VDC ± 10%
Sinking current (mA) 16 mA or less