Parameter Details
11
11.7 F: Options
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 835
Example settings:
When you use these settings, and the monitored output voltage is at 100% (drive rated current), the output voltage
of terminal V1 is 5 V (50% of 10 V). The output current is 200% of the drive rated current when terminal V1
outputs a maximum voltage of 10 V.
• F4-01 [Terminal V1 Function Selection] = 102 (U1-02: Output Frequency)
• F4-02 = 50.0%
• F4-05 [Terminal V1 Bias] = 0.0%
• F4-07 = 0 (0 V to 10 V)
■ F4-03: Terminal V2 Function Selection
No.
(Hex.)
Name Description
Default
(Range)
F4-03
(0393)
Terminal V2
Function Selection
Sets the number for monitor item of output from terminal V2.
103
(000 - 999)
Enter the last three digits of Ux-xx [Monitors] to set monitor data to output from the option card. For example, set
x-xx to 103 to monitor U1-03 [Output Current].
Note:
• You cannot use all of the monitors in all of the control methods.
• When you use the terminal in through mode, set 000 or 031. You can use this setting to adjust the V2 terminal output from PLC
through MEMOBUS/Modbus communications or a communications option.
■ F4-04: Terminal V2 Gain
No.
(Hex.)
Name Description
Default
(Range)
F4-04
(0394)
RUN
Terminal V2 Gain
Sets the gain of the monitor signal that is sent from terminal V2.
50.0%
(-999.9 - +999.9%)
The maximum output voltage output from terminal V2 is ±10 V. Use F4-08 [Terminal V2 Signal Level] to set the
signal level.
Example settings:
When you use these settings, and the monitored output voltage is at 100% (drive rated current), the output voltage
of terminal V2 is 5 V (50% of 10 V). The output current is 200% of the drive rated current when terminal V2
outputs a maximum voltage of 10 V.
• F4-03 [Terminal V2 Function Selection] = 103 (U1-03: Output Current)
• F4-04 = 50.0%
• F4-06 [Terminal V2 Bias] = 0.0%
• F4-08 = 0 (0 V to 10 V)
■ F4-05: Terminal V1 Bias
No.
(Hex.)
Name Description
Default
(Range)
F4-05
(0395)
RUN
Terminal V1 Bias
Sets the bias of the monitor signal that is sent from terminal V1. Set the
level of the analog signal sent from the V1 terminal at 10 V or 20 mA as
100% when an output for monitoring items is 0%.
0.0%
(-999.9 - +999.9%)
The maximum output voltage output from terminal V1 is ±10 V. Use F4-07 [Terminal V1 Signal Level] to set the
signal level.