10.18 Parameters that Change from the Default Settings with A1-02 [Control Method Selection]
616 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
No. Name
Setting
Range
Unit
Control Method (A1-02 Setting)
V/f
(0)
CL-V/f
(1)
OLV
(2)
CLV
(3)
AOLV
(4)
L1-01
Motor
Overload
(oL1)
Protection
0 - 4 1 1 1 1 1 1
L3-05
Stall
Prevention
during RUN
0 - 3 1 1 1 - - -
L3-20
DC Bus
Voltage
Adjustment
Gain
0.00 - 5.00 0.01 1.00 1.00 0.30 0.30 0.30
L3-21
OVSuppres
sion Accel/
Decel P Gain
0.10 - 10.00 0.01 1.00 1.00 1.00 1.00 1.00
L3-36
Current
Suppression
Gain@Accel
0.0 - 100.0 0.1 10.0 10.0 20.0 - -
L4-01
Speed Agree
Detection
Level
0.0 - 400.0
*7
0.1 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz
L4-02
Speed Agree
Detection
Width
0.0 - 20.0 0.1 2.0 Hz 2.0 Hz 2.0 Hz 2.0 Hz 2.0 Hz
L4-03
Speed Agree
Detection
Level(+/-)
-400.0 -
+400.0
*8
0.1 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz
L4-04
Speed Agree
Detection
Width(+/-)
0.0 - 20.0 0.1 2.0 Hz 2.0 Hz 2.0 Hz 2.0 Hz 2.0 Hz
L8-38
Carrier
Frequency
Reduction
0 - 2 1
*3 *3 *3 *3 *3
L8-40
Carrier Freq
Reduction
Off-Delay
0.00 - 2.00 0.01 s 0.50 0.50 0.50 0.50 0.50
n1-15
PWM
Voltage
Offset
Calibration
0 - 2 1 1 1 1 1 2
o1-03
Frequency
Display Unit
Selection
0 - 3 1 0 0 0 0 0
o1-04
V/f Pattern
Display Unit
0 - 1 1 - - - 0 0
*1 Drive models 2211 to 2415 and 4103 to 4675 use these default settings when C6-01 = 1 [Normal / Heavy Duty Selection = Normal
Duty Rating]. Drive models 2257 to 2415, 4140 to 4675 use these default settings when C6-01 = 0 [Heavy Duty Rating].
• A1-02 = 2 [Open Loop Vector]:2.00
• A1-02 = 3, 4 [Closed Loop Vector, Advanced Open Loop Vector]:0.05
*2 The default setting is 1000 ms for drive models 2110 to 2415 and 4103 to 4675.
*3 The default setting varies depending on the setting of C6-01 [Normal / Heavy Duty Selection].
*4 The setting range varies depending on the setting of E5-01 [PM Motor Code Selection] when A1-02 = 5 [Control Method Selection
= PM Open Loop Vector].
*5 The default setting varies depending on drive model and E1-03 [V/f Pattern Selection] settings.
*6 This is the value for 200 V class drives. Double the value for 400 V class drives.
*7 The maximum value within the setting range is 100.0 when A1-02 = 5 or 7 [Control Method Selection = PM Open Loop Vector or
PM Closed Loop Vector].
*8 The setting range is -100.0 to 100.0 when A1-02 = 5 or 7 [Control Method Selection = PM Open Loop Vector or PM Closed Loop
Vector].