Parameter List
10
10.18 Parameters that Change from the Default Settings with A1-02 [Control Method Selection]
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 617
◆ A1-02 = 5 to 8 [Control Method for PM Motors and EZ Vector Control]
No. Name
Setting
Range
Unit
Control Method (A1-02 Setting)
OLV/PM
(5)
AOLV/PM
(6)
CLV/PM
(7)
EZOLV
(8)
b2-01
DC Injection/Zero
SpeedThreshold
0.0 - 10.0 0.1 0.5 Hz 1.0% 0.5% 1.0%
b2-04
DC Inject Braking
Time at Stop
0.00 - 10.00 0.01 s 0.00 0.00 0.00 0.00
b3-01
Speed Search at
Start Selection
0 - 1 1 0 0 1 0
b3-14
Bi-directional
Speed Search
0 - 1 1 1 1 1 1
b5-15
PID Sleep
Function Start
Level
0.0 - 400.0
*1
0.1 0.0 Hz 0.0 % 0.0 % 0.0 %
b6-01
Dwell Reference
at Start
0.0 - 400.0
*1
0.1 0.0 Hz 0.0 % 0.0 % 0.0 %
b6-03
Dwell Reference
at Stop
0.0 - 400.0
*1
0.1 0.0 Hz 0.0 % 0.0 % 0.0 %
b8-02
Energy Saving
Gain
0.0 - 10.0 0.1 - - - -
b8-03
Energy Saving
Filter Time
0.00 - 10.00 0.01 s - - - -
C1-11
Accel/Decel Time
Switchover Freq
0.0 - 400.0
*1
0.1 0.0 Hz 0.0 % 0.0 % 0.0 %
C2-01
S-Curve Time @
Start of Accel
0.00 - 10.00 0.01 s 1.00 0.20 0.20 1.00
C3-01
Slip
Compensation
Gain
0.0 - 2.5 0.1 - - -
Determined by
E9-01
C3-02
Slip
Compensation
Delay Time
0 - 10000 1 ms - - - 200
C4-01
Torque
Compensation
Gain
0.00 - 2.50 0.01 0.00 - - 0.00
C4-02
Torque
Compensation
Delay Time
0 - 10000 1 ms 100 - - 100
C5-01
ASR Proportional
Gain 1
0.00 - 300.00 0.01 10.00 10.00 20.00 10.00
C5-02
ASR Integral
Time 1
0.000 - 60.000 0.001 s 0.500 0.500 0.500 0.500
C5-03
ASR Proportional
Gain 2
0.00 - 300.00 0.01 - 10.00 20.00 10.00
C5-04
ASR Integral
Time 2
0.000 - 10.000 0.001 s - 0.500 0.500 0.500
C5-06 ASR Delay Time 0.000 - 0.500 0.001 s - 0.016 0.004 0.004
C5-07
ASR Gain
Switchover
Frequency
0.0 - 400.0
*1
0.1 0.0 Hz 0.0 % 0.0 % 0.0 %
C6-02
Carrier Frequency
Selection
1 - F 1 2 2 2 2
d3-01 Jump Frequency 1 0.0 - 400.0
*1
0.1 0.0 Hz 0.0 % 0.0 % 0.0 %
d3-02 Jump Frequency 2 0.0 - 400.0
*1
0.1 0.0 Hz 0.0 % 0.0 % 0.0 %
d3-03 Jump Frequency 3 0.0 - 400.0
*1
0.1 0.0 Hz 0.0 % 0.0 % 0.0 %