Parameter List
10
10.18 Parameters that Change from the Default Settings with A1-02 [Control Method Selection]
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 615
No. Name
Setting
Range
Unit
Control Method (A1-02 Setting)
V/f
(0)
CL-V/f
(1)
OLV
(2)
CLV
(3)
AOLV
(4)
C5-02
ASR Integral
Time 1
0.000 -
60.000
0.001 s - 0.200 - 0.500 0.500
C5-03
ASR
Proportional
Gain 2
0.00 - 300.00 0.01 - 0.02 - 20.00 10.00
C5-04
ASR Integral
Time 2
0.000 -
10.000
0.001 s - 0.050 - 0.500 0.500
C5-06
ASR Delay
Time
0.000 - 0.500 0.001 s - - - 0.004 0.004
C5-07
ASR Gain
Switchover
Frequency
0.0 - 400.0 0.1 Hz 0.0 0.0 0.0 0.0 0.0
C6-02
Carrier
Frequency
Selection
1 - F 1 1
*3
1
*3
1
*3
1 1
d3-01
Jump
Frequency 1
0.0 - 400.0 0.1 Hz 0.0 0.0 0.0 0.0 0.0
d3-02
Jump
Frequency 2
0.0 - 400.0 0.1 Hz 0.0 0.0 0.0 0.0 0.0
d3-03
Jump
Frequency 3
0.0 - 400.0 0.1 Hz 0.0 0.0 0.0 0.0 0.0
d3-04
Jump
Frequency
Width
0.0 - 20.0 0.1 Hz 1.0 1.0 1.0 1.0 1.0
d5-02
Torque
Reference
Delay Time
0 - 1000 1 ms - - - 0 0
E1-04
Maximum
Output
Frequency
40.0 - 400.0
*3 *4
0.1 Hz 60.0
*5
60.0
*5
60.0 60.0 60.0
E1-05
Maximum
Output
Voltage
0.0 - 255.0
*6
0.1 V 200.0
*5
200.0
*5
200.0 200.0 200.0
E1-06
Base
Frequency
0.0 - 400.0
*4
0.1 Hz 60.0
*5
60.0
*5
60.0 60.0 60.0
E1-07
Mid Point A
Frequency
0.0 - 400.0
*4
0.1 Hz 3.0
*5
3.0
*5
3.0 0.0 3.0
E1-08
Mid Point A
Voltage
0.0 - 255.0
*6
0.1 V 15.0
*5
15.0
*5
11.0 0.0 10.0
E1-09
Minimum
Output
Frequency
0.0 - 400.0
*4
0.1 Hz 1.5
*5
1.5
*5
0.5 0.0 0.6
E1-10
Minimum
Output
Voltage
0.0 - 255.0
*6
0.1 V 9.0
*5
9.0
*5
2.0 0.0 2.0
F1-01
Encoder 1
Pulse Count
(PPR)
0 - 60000 1 ppr 600 600 600 600 600
F1-05
Encoder 1
Rotation
Selection
0 - 1 1 0 0 0 0 0
F1-09
Overspeed
Detection
Delay Time
0.0 - 2.0 0.1 s - 1.0 - 0.0 0.1
H4-20
Analog
Power
Monitor
100% Level
0.00 - 650.00 0.01
Default value
of E2-11
Default value
of E2-11
Determined
by E2-11
Determined
by E2-11
Determined
by E2-11