Parameter Details
11
11.7 F: Options
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 841
■ F6-01: Communication Error Selection
No.
(Hex.)
Name Description
Default
(Range)
F6-01
(03A2)
Communication Error
Selection
Sets the method to stop the motor or let the motor continue operating when
the drive detects a bUS [Option Communication Error].
1
(0 - 5)
0 : Ramp to Stop
The drive ramps to stop in the set deceleration time. Fault relay output terminal MA-MC activates and terminal
MB-MC deactivates.
1 : Coast to Stop
The drive output shuts off and the motor coasts to stop. Fault relay output terminal MA-MC activates and terminal
MB-MC deactivates.
2 : Fast Stop (Use C1-09)
The drive stops the motor in the deceleration time set in C1-09 [Fast Stop Time]. Fault relay output terminal MA-
MC activates and terminal MB-MC deactivates.
3 : Alarm Only
The keypad shows bUS and the drive continues operation at the current frequency reference.
Note:
Separately prepare safety protection equipment and systems, for example fast stop switches.
The output terminal set for Alarm [H2-01 to H2-03 = 10] activates.
4 : Alarm (Run at d1-04)
The keypad shows bUS and the drive continues operation at the speed set in d1-04 [Reference 4].
Note:
Separately prepare safety protection equipment and systems, for example fast stop switches.
5 : Alarm - Ramp Stop
The drive stops the motor during the deceleration time set in C1-02 [Deceleration Time 1].
After you remove the bUS alarm, the motor will accelerate to the previous frequency reference.
■ F6-02: Comm External Fault (EF0) Detect
No.
(Hex.)
Name Description
Default
(Range)
F6-02
(03A3)
Comm External Fault
(EF0) Detect
Sets when the drive will detect EF0 [Option Card External Fault] is
detected.
0
(0, 1)
0 : Always Detected
1 : Detected during RUN Only
■ F6-03: Comm External Fault (EF0) Select
No.
(Hex.)
Name Description
Default
(Range)
F6-03
(03A4)
Comm External Fault
(EF0) Select
Sets the method to stop the motor or let the motor continue operating when
the drive detects an EF0 [Option Card External Fault].
1
(0 - 3)
0 : Ramp to Stop
The drive ramps to stop in the set deceleration time. Fault relay output terminal MA-MC activates and terminal
MB-MC deactivates.
1 : Coast to Stop
The drive output shuts off and the motor coasts to stop. Fault relay output terminal MA-MC activates and terminal
MB-MC deactivates
2 : Fast Stop (Use C1-09)