Parameter Details
11
11.7 F: Options
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 843
F6-10: CC-Link Node Address
No.
(Hex.)
Name Description
Default
(Range)
F6-10
(03B6)
CC-Link Node
Address
Sets the node address for CC-Link communication. Restart the drive after
changing this setting.
0
(0 - 64)
Note:
Be sure to set a node address that is different than all other node addresses. Do not set this parameter to 0. Incorrect parameter settings
will cause AEr [Station Address Setting Error] errors and the L.ERR LED on the option will come on.
When the only drive is connected, you can connect a maximum of 42 nodes. Follow these rules to connect devices
that are not drives:
{(1 × a) + (2 × b) + (3 × c) + (4 × d)} 64
(a: number of units that occupies 1 node, b: number of units that occupies 2 nodes, c: number of units that
occupies 3 nodes, d: number of units that occupies 4 nodes)
{(16 × A) + (54 × B) + (88 × C)} 2304
(A: number of remote I/O nodes (64 max.), B: number of remote device nodes (42 max.), C: number of local
nodes (26 max.))
F6-11: CC-Link Communication Speed
No.
(Hex.)
Name Description
Default
(Range)
F6-11
(03B7)
CC-Link
Communication
Speed
Sets the communication speed for CC-Link communication. Restart the
drive after you change this setting.
0
(0 - 4)
0 : 156 kbps
1 : 625 kbps
2 : 2.5 Mbps
3 : 5 Mbps
4 : 10 Mbps
F6-14: BUS Error Auto Reset
No.
(Hex.)
Name Description
Default
(Range)
F6-14
(03BB)
BUS Error Auto
Reset
Sets the automatic reset function for bUS [Option Communication Errors].
0
(0, 1)
0 : Disabled
1 : Enabled
F6-16: Gateway Mode
No.
(Hex.)
Name Description
Default
(Range)
F6-16
(0B8A)
Gateway Mode
Sets the gateway mode operation and the number of connected slave drives.
0
(0 - 4)
0 : Disabled
1 : Enabled: 1 Slave Drive
2 : Enabled: 2 Slave Drives
3 : Enabled: 3 Slave Drives
4 : Enabled: 4 Slave Drives
Gateway Mode processes communications through internal the RS-485 communication function to relay data
from a drive that has the communication option to more than one drive that does not have the communication
option. This function lets you use fieldbus communication to connect a maximum of 5 drives with only one
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA GA700

Related product manuals