3.11 Test Run Checklist
216 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Check No. Description
17 Set F1-01 [Encoder 1 Pulse Count (PPR)] and F1-05 [Encoder 1 Rotation Selection].
18 Set E5-11 [Encoder Z-Pulse Offset].
Check No. Description
19 The keypad will show “Rdy” after starting to operate the motor.
20
To give the Run command and frequency reference from the keypad, push to set to LOCAL Mode (when
in LOCAL Mode, the LO/RE LED illuminates).
21 If the motor rotates in the opposite direction during test run, switch two of the motor cables (U/T1, V/T2, W/T3).
22
Set Heavy Duty or Normal Duty Mode with C6-01 [Normal / Heavy Duty Selection] to conform to the load
condition.
23
Set E2-01 [Motor Rated Current (FLA)] and L1-01 [Motor Overload Protection Select] correctly for motor
thermal protection.
24
Set the drive for REMOTE Mode when the control circuit terminals supply the Run command and frequency
reference (in REMOTE Mode, the LO/RE LED turns OFF).
25
When terminal A1 is used for the frequency reference:
• Voltage input
– Set DIP Switch S1-1 on the drive to “V”.
– Set H3-01 = 0, 1 [Terminal A1 Signal Level Select = 0 to 10V (Lower Limit at 0), -10 to +10V (Bipolar
Reference)].
– Set H3-02 = 0 [Terminal A1 Function Selection = Frequency Reference].
• Current input
– Set DIP Switch S1-1 on the drive to “I”.
– Set H3-01 = 2, 3 [Terminal A1 Signal Level Select = 4 to 20 mA, 0 to 20 mA].
– Set H3-02 = 0 [Terminal A1 Function Selection = Frequency Reference].
26
When terminal A2 is used for the frequency reference:
• Voltage input
– Set DIP Switch S1-2 on the drive to “V.
– Set H3-09 = 0, 1 [Terminal A2 Signal Level Select = 0 to 10V (Lower Limit at 0), -10 to +10V (Bipolar
Reference)].
– Set H3-10 = 0 [Terminal A2 Function Selection = Frequency Reference].
• Current input
– Set DIP Switch S1-2 on the drive to “I”.
– Set H3-09 = 2, 3 [Terminal A2 Signal Level Select = 4 to 20 mA, 0 to 20 mA].
– Set H3-10 = 0 [Terminal A2 Function Selection = Frequency Reference].