EasyManua.ls Logo

YASKAWA GA700 - Page 309

YASKAWA GA700
1053 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Network
Communications
5
5.3 MEMOBUS/Modbus Communications
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 309
Register No.
(Hex.)
Description
002A
Minor Fault Description 1
bit 0 - 1 Reserved
bit 2 EF [FWD/REV Run Command Input Error]
bit 3 bb [Baseblock]
bit 4 oL3 [Overtorque 1]
bit 5 oH [Heatsink Overheat]
bit 6 ov [DC Bus Overvoltage]
bit 7 Uv [Undervoltage]
bit 8 FAn [Internal Fan Fault]
bit 9 CE [Modbus Communication Error]
bit A bUS [Option Communication Error]
bit B UL3/UL4 [Undertorque Detection 1/2]
bit C oH3 [Motor Overheat (PTC Input)]
bit D FbL [PID Feedback Loss], FbH [Excessive PID Feedback]
bit E Reserved
bit F CALL [Serial Comm Transmission Error]
002B
U1-10 [Input Terminal Status]
bit 0 1: Control circuit terminal S1 ON
bit 1 1: Control circuit terminal S2 ON
bit 2 1: Control circuit terminal S3 ON
bit 3 1: Control circuit terminal S4 ON
bit 4 1: Control circuit terminal S5 ON
bit 5 1: Control circuit terminal S6 ON
bit 6 1: Control circuit terminal S7 ON
bit 7 1: Control circuit terminal S8 ON
bit 8 - F Reserved

Table of Contents

Other manuals for YASKAWA GA700