6.4 Faults
360 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Code Name Causes Possible Solutions
The relay or contactor on the soft-charge
bypass relay is damaged.
U4-06 [PreChargeRelayMainte] shows the
performance life of the soft-charge bypass relay. If
U4-06 is more than 90%, replace the board or the
drive. For information about replacing the board,
contact Yaskawa or your nearest sales
representative.
Note:
The drive detects this error if the DC bus voltage decreases below the level set in L2-05 [Undervoltage Detection Lvl (Uv1)] while the
drive is running.
The Uv1 detection level is approximately 190 V for a 200 V class drives. The detection level is approximately 380 V for 400 V class
drives. The detection level is approximately 350 V when E1-01 [Input AC Supply Voltage] < 400.
Do a Fault Reset to clear the fault.
Fault trace is not available for this fault.
L5-08 [Fault Reset Enable Select Grp2] disables the Auto Restart function.
Code Name Causes Possible Solutions
Uv2 Control Power
Undervoltage
The value set in L2-02 [Power Loss
Ride Through Time] increased and the
momentary power loss recovery unit is
not connected to the drive.
Connect the momentary power loss recovery unit
to the drive.
There was a problem with the drive
hardware.
Re-energize the drive.
If the fault stays, replace the control board or the
drive. For information about replacing the
control board, contact Yaskawa or your nearest
sales representative.
Note:
The drive detects this error if the control power supply voltage decreases.
Do a Fault Reset to clear the fault.
Fault trace is not available for this fault.
Code Name Causes Possible Solutions
Uv3 Soft Charge Answerback
Fault
The relay or contactor on the soft-charge
bypass relay is damaged.
Re-energize the drive.
If the fault stays, replace the control board or the
drive.
Check monitor U4-06 [PreChargeRelayMainte]
shows the performance life of the soft-charge
bypass relay. If U4-06 is more than 90%, replace
the board or the drive. For information about
replacing the board, contact Yaskawa or your
nearest sales representative.
Note:
Do a Fault Reset to clear the fault.
Fault trace is not available for this fault.