10.17 U: Monitors
608 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
No.
(Hex.)
Name Description
MFAO Signal
Level
Ref.
U4-21
(07DD)
Run Command
Source
Shows the selected Run command source.
The keypad shows the Run command source as XY-nn as specified
by these rules:
X: External Reference 1/2 Selection [H1-xx = 2] selection status
1: b1-02 [Run Command Selection 1]
2: b1-16 [Run Command Selection 2]
Y: Run command source
0: Keypad
1: Control circuit terminal
3: MEMOBUS/Modbus communications
4: Communication option card
7: DriveWorksEZ
nn: Run command limit status data
00: No limit status.
01: The Run command was left ON when the drive stopped in the
Programming Mode.
02: The Run command was left ON when switching from
LOCAL Mode to REMOTE Mode.
03: The Run command is in standby after the drive was energized
until the soft charge bypass contactor turns ON.
Note:
The drive will detect Uv1 [DC Bus Undervoltage] or Uv
[Undervoltage] if the soft charge bypass contactor does not turn
ON after 10 s.
04: Restart after run stop is prohibited.
05: Fast stop has been executed using the MFDI terminal. Or, the
motor has ramped to stop by pressing the STOP key on the
keypad.
06: b1-17 = 0 [Run Command at Power Up = Disregard Existing
RUN Command] is set.
07: During baseblock while coast to stop with timer.
08: Frequency reference is below E1-09 [Minimum Output
Frequency] during baseblock.
09: Waiting for the Enter command from PLC.
No signal output
The keypad shows
the Run command
source as "XY-nn"
as specified by
these rules:
available
-
U4-22
(07DE)
Modbus CmdData
(hex)
Shows the operation signal (register 0001H) sent to the drive from
MEMOBUS/Modbus communications as a 4-digit hexadecimal
number (zero suppress). The keypad shows the operation signal as
specified by these rules:
bit 0 : Forward run/Stop
bit 1 : Reverse run/Stop
bit 2 : External fault
bit 3 : Fault Reset
bit 4 : Multi-function input 1
bit 5 : Multi-function input 2
bit 6 : Multi-function input 3
bit 7 : Multi-function input 4
bit 8 : Multi-function input 5
bit 9 : Multi-function input 6
bit A : Multi-function input 7
bit B : Multi-function input 8
bit C : Not used (normal value of 0).
bit D : Not used (normal value of 0).
bit E : Not used (normal value of 0).
bit F : Not used (normal value of 0).
No signal output
available
-
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV