2.11 Electrical Installation
74 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Figure 2.68 Standard Drive Connection Diagram
*1 Set the wiring sequence to de-energize the drive with the fault relay output. If the drive outputs a fault during
fault restart when you use the fault restart function, set L5-02 = 1 [Fault Contact at Restart Select = Always
Active] to de-energize the drive. Be careful when you use a cut-off sequence. The default setting for L5-02 is
0 [Active Only when Not Restarting].
*2 When you install a DC reactor, you must remove the jumper between terminals +1 and +2.