11.7 F: Options
830 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
■ F3-01: Digital Input Function Selection
No.
(Hex.)
Name Description
Default
(Range)
F3-01
(0390)
Digital Input
Function Selection
Sets the data format of digital input signals. Set o1-03 = 0 or 1 [Frequency
Display Unit Selection = 0.01 Hz or 0.01% (100% = E1-04)] to enable this
function.
0
(0 - 8)
Note:
The input signal type is BCD when o1-03 = 2 or 3 [Revolutions Per Minute (RPM) or User Units (o1-10 & o1-11)]. The o1-03 value
sets the setting units.
0 : BCD, 1% units
1 : BCD, 0.1% units
2 : BCD, 0.01% units
3 : BCD, 1 Hz units
4 : BCD, 0.1 Hz units
5 : BCD, 0.01 Hz units
6 : BCD (5-digit), 0.01 Hz
7 : Binary input
The setting unit and setting range vary depending on the value set in F3-03 [Digital Input Data Length Select].
• F3-03 = 0 [8-bit]: 100%/255 (-255 to +255)
• F3-03 = 1 [12-bit]: 100%/4095 (-4095 to +4095)
• F3-03 = 2 [16-bit]: 100%/30000 (-33000 to +33000)
8 : Multi-Function Digital Input
The DI-A3 card is also used as a multi-function digital input terminal.
■ F3-03: Digital Input Data Length Select
No.
(Hex.)
Name Description
Default
(Range)
F3-03
(03B9)
Digital Input Data
Length Select
Sets the number of bits to set the frequency reference with DI-A3.
2
(0 - 2)
0 : 8-bit
1 : 12-bit
2 : 16-bit