11.8 H: Terminal Functions
890 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
0 : 0.1 kWh units
1 : 1 kWh units
2 : 10 kWh units
3 : 100 kWh units
4 : 1000 kWh units
■ H2-07: Modbus Register 1 Address Select
No.
(Hex.)
Name Description
Default
(Range)
H2-07
(0B3A)
Modbus Register 1
Address Select
Sets the address of the MEMOBUS/Modbus register output to the MFDO
terminal.
0001
(0001 - 1FFF)
Configures H2-07 with the address of the register that is output to Modbus Reg 1 Status Satisfied [H2-01 to H2-03
= 62] and configures H2-08 with the bit.
■ H2-08: Modbus Register 1 Bit Select
No.
(Hex.)
Name Description
Default
(Range)
H2-08
(0B3B)
Modbus Register 1
Bit Select
Sets the bit of the MEMOBUS/Modbus register output to the MFDO
terminal.
0000
(0000 - FFFF)
Sets the bit of the register that is output to Modbus Reg 1 Status Satisfied [H2-01 to H2-03 = 62] and uses the
address in H2-07 [Modbus Register 1 Address Select].
■ H2-09: Modbus Register 2 Address Select
No.
(Hex.)
Name Description
Default
(Range)
H2-09
(0B3C)
Modbus Register 2
Address Select
Sets the address of the MEMOBUS/Modbus register output to the MFDO
terminal.
0001
(0001 - 1FFF)
Sets H2-09 with the address of the register that is output to Modbus Reg 2 Status Satisfied [H2-01 to H2-03 = 63]
and uses the bit in H2-10 [Modbus Register 2 Bit Select].
■ H2-10: Modbus Register 2 Bit Select
No.
(Hex.)
Name Description
Default
(Range)
H2-10
(0B3D)
Modbus Register 2
Bit Select
Sets the bit of the MEMOBUS/Modbus register output to the MFDO
terminal.
0000
(0000 - FFFF)
Sets the bit of the register that is output to Modbus Reg 2 Status Satisfied [H2-01 to H2-03 = 63] and uses the
address in H2-09.
■ H2-20: Comparator 1 Monitor Selection
No.
(Hex.)
Name Description
Default
(Range)
H2-20
(1540)
Comparator 1
Monitor Selection
Sets the monitor number for comparator 1. Set the x-xx part of the Ux-xx
[Monitor]. For example, set x-xx to 102 to monitor U1-02 [Output
Frequency].
102
(000 - 999)
Note:
• Refer to H2-xx = 66 and 67 [MFDO Function Select = Comparator1 and Comparator2] for more information about the comparator
function.
• The configurable monitor changes when the control method changes.