Doc ID :ADR233B/IM/01
Ref ID : ADR233B/IM/UG
Rev No. : 05
ADR233B
Ph Differential
Slope2
80 %
Range 15 – 150%
Editable Setting
By using the Plus / Up arrow key (+ /) or the Minus / Down
arrow key (- /) the Slope2 can be set.
The setting range is from 15 to 150% in step of 1%.
Press the Minus / Down arrow key (- /) to move to the next
option.
Ph Differential
tIs>
0.01 s
Range 0 – 10s
Editable Setting
By using the Plus / Up arrow key (+ /) or the Minus / Down
arrow key (- /) the tIs> can be set.
The setting range is from 0 to 10s in step of 0.1s.
Press the Minus / Down arrow key (- /) to move to the next
option.
Ph Differential
IHs>1
10.0 pu
Range 0.5 – 30pu
Editable Setting
By using the Plus / Up arrow key (+ /) or the Minus / Down
arrow key (- /) the IHs>1 can be set.
The setting range is from 0.5 to 30pu in step of 0.1pu.
Press the Minus / Down arrow key (- /) to move to the next
option.
Ph Differential
IHs>2
10.0 pu
Range 0.5 – 30pu
Editable Setting
By using the Plus / Up arrow key (+ /) or the Minus / Down
arrow key (- /) the IHs>2 can be set.
The setting range is from 0.5 to 30pu in step of 0.1pu.
Press the Left arrow key () to move to the next option.
Ph Differential
Ph Differential
Enabled
Editable Setting
By using the Plus / Up arrow key (+ /) or the Minus / Down
arrow key (- /) the Ph Differential can be set i.e. Disabled /
Enabled.
Press the Minus / Down arrow key (- /) to move to the next
option.