EasyManua.ls Logo

Ashida ADR233B - Page 473

Default Icon
479 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Doc ID : ADR233B_IM_01
Ref ID : ADR233B/IM/TC
Rev No. : 05
Page No. : 473 of 479
ADR233B
OUT Zone Fault:
Apply suitable 3 phase 440V source to HV side of transformer before CT.
Keep R phase shorted of LV side of transformer after CT. (Keep grounded, if transformer is
grounded).
Y
3 Phase
440V
Supply
Measure the Primary current at CT terminal & Secondary current at relay CT terminal using
Clamp meter/ Tong tester.
Observe & note down the primary & secondary current on Relay Measurement window.
Repeat the above procedure for Y & B phase, phase to phase and 3 phase faults.
Primary Current
Relay CT Terminal Current
HV LV
HV LV
EF
R Y B R Y B
R Y B R Y B
Relay Display Current
HV LV
EF
Differ Current Bias Current
REF Low
Imp.
REF
High Z
W1 R W1 Y W1 B W2 R W2 Y W2 B Id R Id Y Id B Ib R Ib Y Ib B Id Ib IREF
11.4.3 Pick up and Trip Test
Connect current source at winding 1 R-phase CT terminals 1A/5A current input terminal
Set current setting value to 100% i.e. 1A/5A, TMS at Minimum (x0.01) value.
Start current injector & increase current value till relay get pick up and trip. The operating
value should be within 1 to 1.1 times of set pickup value.
Select the Curve IEC S Inverse and Set the TMS at 1.00.
Connect the assigned trip contact to Timer.
Set and apply 2 times current value and measure the timing on timer.
The measured timing should be ±5% of actual timing i.e. 10.029 Sec.
Repeat the above procedure for remaining phases and Earth Fault.

Table of Contents

Related product manuals