Manual Boost 73
User Guide v 2.0 — March 2023 Making Adjustments
7.8.1.5 Manual Boost
The Manual Boost fields are described in Table 7-11.
7.8.1.6 Remote Standby
The Remote Standby fields are described in Table 7-12.
Table 7-11 Manual Boost Fields
Item Description
Temperature Setpoint The temperature to which all zones are set when the Boost button is
touched. This setting raises all zones to their manual boost setpoint until
the timer completes or the user touches the Boost button again. Possible
values are 0 to 500 °C or 32 to 932 °F. The default value is No Change.
Temperature Minimum
These values specify the range limits in which the Boost Temperature can
be set.
Temperature Maximum
Power Setpoint The power values to which all zones are set when the Boost button is
touched. This setting raises all zones to their manual boost setpoint until
the timer completes or the user touches the Boost button again. Possible
values are 0% – 100%. The default value is 90%.
Power Minimum
These values specify the percentage range limits in which the Boost
power can be set.
Power Maximum
Table 7-12 Remote Standby Fields
Item Description
Temperature Setpoint Remote standby is started by a digital input signal from the Injection
Molding Machine (IMM). This setting lowers all zones to their remote
standby temperature setpoint until the timer completes or the input
signal is off. Possible values are 0 to 500 °C or 32 to 932 °F. The default
value is 121 °C or 250 °F.
Temperature Minimum
These values specify the range limits in which the Remote Standby
Temperature can be set.
Temperature Maximum
Power Setpoint Remote standby is started by a digital input signal from the IMM. This
setting lowers all zones to their remote standby power setpoint until the
timer completes or the input signal is off. Possible values are 0% – 100%.
The default value is 10%.
Power Minimum
These values specify the percentage range limits in which the Remote
Standby Power can be set.
Power Maximum