Optional Priority Control Mode (PCM) Digital Output 85
User Guide v 2.0 — March 2023 Making Adjustments
Optional Priority Control Mode (PCM) Digital Output
If the PCM digital output option is turned on, it will be activated only when a zone that is set
to System mode has an abort condition. It will stay in this state until the PCM error is reset.
7.8.11 Change the Earth Leakage Check
When started, the Altanium system does a check of the earth leakage conditions on every
heater in the mold. When necessary, the system will start a low voltage, phase angle bake out
on the faulty zone(s) to try to bake the moisture out of the heater(s).
The Earth Leakage Check can be set to ON or OFF for each zone. The default is ON for all
zones. You would have the Earth Leakage Check set to OFF only in special conditions. To
change the Earth Leakage Check to OFF globally for the full system, please contact the
nearest Husky Regional Service and Sales office.
7.8.12 Change the Automatic Manual Control
If there is a thermocouple malfunction during an operation, the Altanium system can
automatically apply a manual power output percentage to the heater, calculated from the
data information collected before the thermocouple failed. This feature is the Automatic
Manual Control (AMC).
If a thermocouple fails and the AMC is set to ON, the control changes the failed zone to
Manual mode and sets a manual power output, calculated from the previously recorded
average power output to that heater. If the AMC is set to OFF, the control changes to PCM
and does the designated task. The default setting is ON for all zones.
To change the AMC setting for a zone, do the steps that follow:
1. Touch the zone to be changed.
2. Touch the Advanced Settings drop-down tab.
3. Touch the AMC - Automatic Manual Control field.
4. Select On or Off in the AMC - Automatic Manual Control dialog window.
7.8.13 Change the Output Power Limit Setting
The Output Power Limit lets users set the maximum amount of power that can be supplied
to the heaters. The default power limit for all zones is 100%.
To change the Output Power Limit for a zone, do the steps that follow:
1. Touch the zone to be changed.
2. Touch the Advanced Settings drop-down tab.
3. Touch the Output Power Limit field.
4. Type a value from 0% to 100% in the Output Power Limit dialog window.
5. Touch the Accept button.