Sequencing Logic B-4
AC30V series Variable Speed Drive
Transition 1: NOT READY TO SWITCH ON to SWITCH ON DISABLED
Automatic transition when initialisation has been completed and application has been loaded.
Transition 2: SWITCH ON DISABLED to READY TO SWITCH ON
Shutdown command received from control device or local signal.
Transition 3: READY TO SWITCH ON to SWITCHED ON
Switch On command received from control device or local signal.
Transition 4: SWITCHED ON to OPERATION ENABLED
Enable Operation (Run Forward, Run Reverse or Jog) command received from control device or local signal.
Transition 5: OPERATION ENABLED to SWITCHED ON
Disable Operation (Stop) command received from control device or local signal and Disabling (Stopping) function completed.
Transition 6: SWITCHED ON to READY TO SWITCH ON
Shutdown command received from control device or local signal.
Transition 7: READY TO SWITCH ON to SWITCH ON DISABLED
Quick Stop or Disable Voltage command received from control device or local signal.
Transition 8: OPERATION ENABLED to READY TO SWITCH ON
Shutdown command received from control device or local signal and Shutdown function completed.
Transition 9: OPERATION ENABLED to SWITCH ON DISABLED
Disable Voltage command received from control device or local signal.
Transition 10: SWITCHED ON to SWITCH ON DISABLED
Disable Voltage or Quick Stop command received from control device or local signal.
Transition 11: OPERATION ENABLED to QUICKSTOP ACTIVE
Quick Stop command received from control device or local signal.
Transition 12: OPERATION ENABLED to QUICKSTOP ACTIVE
Automatic transition when the Quick Stop function is completed or Disable Voltage command received.
Transition 13: any state to FAULT REACTION ACTIVE
Fault (Trip) occurred.
Transition 14: FAULT REACTION ACTIVE to FAULT
Automatic transition when Fault Reaction function completed or Disable Voltage command received.
Transition 15: FAULT to SWITCH ON DISABLED
Fault Reset command received from control device or local signal and there are no active faults.
www.comoso.com

Table of Contents

Other manuals for Parker AC30 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker AC30 series and is the answer not in the manual?

Parker AC30 series Specifications

General IconGeneral
Control ModesClosed-loop vector
FeedbackEncoder
Operating Temperature0 to 40°C (32 to 104°F) standard, -20 to 50°C (-4 to 122°F) with derating
ProtectionOvercurrent, Overvoltage, Undervoltage
CommunicationRS485

Related product manuals