D-46 Parameter Reference 
AC30V series Variable Speed Drive 
General Purpose IO 
Monitor::Inputs and Outputs 
Parameters::Option IO::General Purpose IO 
 
The General Purpose IO parameters configure the use of the three IO Options, (Error! Bookmark not defined.). This group of parameters is 
only visible when an IO Option is selected. 
 
PNO  Parameter Descriptions 
1181  Anin 11 Value, (Terminal X21.2) 
The input value expressed as a percentage of range, (+/- 100%), following Offset and Scale. 
1182  Anin 12 Value, (Terminal X21.3) 
The input value expressed as a percentage of range, (+/- 100%), following Offset and Scale. 
1183  Anin 13 Value, (Terminal X21.4) 
The input value expressed as a percentage of range, (+/- 100%), following Offset and Scale. 
1461  Anin 11 Offset 
The offset is expressed as a percentage of the hardware range. For example an offset of 10% is equivalent to 1V on the input. 
The offset is added to the measured value. 
1462  Anin 11 Scale 
The scale is a simple multiplication factor. The input voltage is converted to a percentage value. 1461 Anin 11 Offset is added and 
the result is multiplied by Scale. The result is presented in parameter 
. 
1463  Anin 12 Offset 
The offset is expressed as a percentage of the hardware range. For example an offset of 10% is equivalent to 1V on the input. 
The offset is added to the measured value. 
1464  Anin 12 Scale 
The scale is a simple multiplication factor. The input voltage is converted to a percentage value. 1463 Anin 12 Offset is added and 
the result is multiplied by Scale. The result is presented in parameter 
. 
1465  Anin 13 Offset 
The offset is expressed as a percentage of the hardware range. For example an offset of 10% is equivalent to 1V on the input. 
The offset is added to the measured value. 
1466  Anin 13 Scale 
The scale is a simple multiplication factor. The input voltage is converted to a percentage value. 1465 Anin 13 Offset is added and 
the result is multiplied by Scale. The result is presented in parameter 
.