Page #331 background image
Parameter Reference D-59
AC30V series Variable Speed Drive
Minimum Speed
Setup::Application::Minimum Speed
Function availability depends on macro selected.
The minimum speed function is used to determine how the AC30V will follow a reference. There are two modes:
Functional Description
There are two operating modes for the MINIMUM SPEED function:
PROP WITH MINIMUM (proportional with minimum)
In this mode the MINIMUM SPEED function behaves like a simple clamp. The Minimum Speed
Value has the valid range -100% to 100% and the output is always greater than or equal to the
Minimum Speed Value.
LINEAR
In this mode the MINIMUM SPEED function first clamps the input to zero then rescales the input such
that the output goes linearly between minimum and 100% for an input that goes from 0 to 100%.
Note the constraints:-
min >= 0
input >= 0
max = 100%
PNO Parameter Descriptions
1906 Minimum Speed Value
Specifies the minimum output value.
1907 Minimum Speed Mode
There are two modes of operation:
Enumerated Value:
0 : PROP WITH MINIMUM
1 : LINEAR
Min
0 100%
100
-100
input
output
www.comoso.com

Table of Contents

Other manuals for Parker AC30 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker AC30 series and is the answer not in the manual?

Parker AC30 series Specifications

General IconGeneral
Control ModesClosed-loop vector
FeedbackEncoder
Operating Temperature0 to 40°C (32 to 104°F) standard, -20 to 50°C (-4 to 122°F) with derating
ProtectionOvercurrent, Overvoltage, Undervoltage
CommunicationRS485