D-106 Parameter Reference 
AC30V series Variable Speed Drive 
Spd Direct Input 
Parameters::Motor Control::Spd Direct Input 
Only apply to SVC control mode, IM or PMAC. 
 
PNO  Parameter Descriptions 
0528  Direct Input Select 
The direct input to the speed loop is an analog input which is sampled synchronously with the speed loop. This ensures that the 
speed loop always has the most up-to-date value of the input, allowing it to respond faster. Either of the two analog inputs can be 
selected as the direct input. If NONE is selected, the input is set to zero. When not in use, it should be disabled by selecting NONE.  
Enumerated Value : Direct IP Select 
0 : NONE 
1 : ANIN1 
2 : ANIN2 
0529  Direct Input Ratio 
The Direct Input is multiplied by this parameter. 
0530  Direct Input Pos Lim 
This limits the upper value of the Direct Input. 
0531  Direct Input Neg Lim 
This limits the lower value of the Direct Input. 
Functional Description 
The Drive is commanded to run the motor at a certain speed, which is derived from various sources, such as comms, analog inputs, commands 
from the keypad, etc.  Most of these are derived from sources which respond relatively slowly, eg every 1ms.  For processes which require a 
faster response, the direct input is provided.  This is an analog input which is sampled synchronously with the speed loop, as described above.  It 
is added on to the other sources of speed command to give a total speed command.