D-136 Parameter Reference
AC30V series Variable Speed Drive
PNO
Name
Path(s)
Type
Default
Range
Units
WQ
View
Notes
MBus
0489
Symmetric Time
Parameters::Motor Control::Ramp
TIME
10.000
0.000 to 3000.000
s
ALWAYS
TECHNICIAN
01505
0490
Sramp Continuous
Parameters::Motor Control::Ramp
BOOL
FALSE
ALWAYS
TECHNICIAN
01507
0491
Sramp Acceleration
Parameters::Motor Control::Ramp
REAL
10.0
0.0 to 100.0
%/s²
ALWAYS
OPERATOR
01509
0492
Sramp Deceleration
Parameters::Motor Control::Ramp
REAL
10.0
0.0 to 100.0
%/s²
ALWAYS
TECHNICIAN
01511
0493
Sramp Jerk 1
Parameters::Motor Control::Ramp
REAL
10.0
0.0 to 100.0
%/s³
ALWAYS
TECHNICIAN
01513
0494
Sramp Jerk 2
Parameters::Motor Control::Ramp
REAL
10.0
0.0 to 100.0
%/s³
ALWAYS
TECHNICIAN
01515
0495
Sramp Jerk 3
Parameters::Motor Control::Ramp
REAL
10.0
0.0 to 100.0
%/s³
ALWAYS
TECHNICIAN
01517
0496
Sramp Jerk 4
Parameters::Motor Control::Ramp
REAL
10.0
0.0 to 100.0
%/s³
ALWAYS
TECHNICIAN
01519
0497
Ramp Hold
Parameters::Motor Control::Ramp
BOOL
FALSE
ALWAYS
TECHNICIAN
01521
0498
Ramping Active
Parameters::Motor Control::Ramp
BOOL
NEVER
TECHNICIAN
01523
0499
Ramp Spd Setpoint Input
Parameters::Motor Control::Ramp
REAL
x.x
-200.0 to 200.0
%
NEVER
TECHNICIAN
01525
0500
Ramp Speed Output
Parameters::Motor Control::Ramp
REAL
x.x
-200.0 to 200.0
%
NEVER
TECHNICIAN
01527
0501
Jog Setpoint
Parameters::Motor Control::Ramp
REAL
10.0
0.0 to 100.0
%
ALWAYS
TECHNICIAN
01529
0502
Jog Acceleration Time
Parameters::Motor Control::Ramp
TIME
1.000
0.000 to 3000.000
s
ALWAYS
TECHNICIAN
01531
0503
Jog Deceleration Time
Parameters::Motor Control::Ramp
TIME
1.000
0.000 to 3000.000
s
ALWAYS
TECHNICIAN
01533
0504
Stop Ramp Time
Same as PNO 484
TIME
10.000
0.000 to 600.000
s
ALWAYS
TECHNICIAN
01535
0505
Zero Speed Threshold
Parameters::Motor Control::Ramp
REAL
0.1
0.0 to 100.0
%
ALWAYS
TECHNICIAN
01537
0506
Zero Speed Stop Delay
Parameters::Motor Control::Ramp
TIME
0.500
0.000 to 30.000
s
ALWAYS
TECHNICIAN
01539
0507
Quickstop Time Limit
Parameters::Motor Control::Ramp
TIME
30.000
0.000 to 3000.000
s
ALWAYS
TECHNICIAN
01541
0508
Quickstop Ramp Time
Parameters::Motor Control::Ramp
TIME
0.100
0.000 to 600.000
s
ALWAYS
TECHNICIAN
01543
0509
Final Stop Rate
Parameters::Motor Control::Ramp
REAL
1200
1 to 4800
Hz/s
ALWAYS
TECHNICIAN
01545
0511
Motor Type
Setup::Motor Control::Control and Type
Parameters::Motor Control::Control Mode
USINT
(enum)
0
0:INDUCTION MOTOR
1:PMAC MOTOR
STOPPED TECHNICIAN 6
01549
0512
Control Strategy Same as PNO 511
USINT
(enum)
0
0:VOLTS - HERTZ
CONTROL
1:VECTOR CONTROL
STOPPED TECHNICIAN 6
01551
0515
Speed Loop Pgain
Parameters::Motor Control::Spd Loop Settings
REAL
20.00
0.00 to 3000.00
ALWAYS
TECHNICIAN
01557
0516
Speed Loop I Time
Parameters::Motor Control::Spd Loop Settings
TIME
0.100
0.001 to 1.500
s
ALWAYS
TECHNICIAN
01559
0517
Speed Loop Int Defeat
Parameters::Motor Control::Spd Loop Settings
BOOL
FALSE
ALWAYS
TECHNICIAN
01561
0518
Speed Loop Int Preset
Parameters::Motor Control::Spd Loop Settings
REAL
0
-500 to 500
ALWAYS
TECHNICIAN
01563
0519
Spd Loop Dmd Filt TC
Parameters::Motor Control::Spd Loop Settings
REAL
0.0
0.0 to 15.0
ms
ALWAYS
TECHNICIAN
01565
0520
Spd Loop Fbk Filt TC
Parameters::Motor Control::Spd Loop Settings
REAL
1.0
0.0 to 15.0
ms
ALWAYS
TECHNICIAN
01567
0521
Spd Loop Aux Torq Dmd
Parameters::Motor Control::Spd Loop Settings
REAL
0.00
-300.00 to 300.00
%
ALWAYS
TECHNICIAN
01569
0523
Spd Loop Adapt Thres
Parameters::Motor Control::Spd Loop Settings
REAL
0.00
0.00 to 10.00
%
ALWAYS
TECHNICIAN
01573
0524
Spd Loop Adapt Pgain
Parameters::Motor Control::Spd Loop Settings
REAL
20.00
0.00 to 300.00
ALWAYS
TECHNICIAN
01575
0525
Spd Demand Pos Lim
Parameters::Motor Control::Spd Loop Settings
REAL
110.00
-110.00 to 110.00
%
ALWAYS
TECHNICIAN
01577
0526
Spd Demand Neg Lim
Parameters::Motor Control::Spd Loop Settings
REAL
-110.00
-110.00 to 110.00
%
ALWAYS
TECHNICIAN
01579
0527
Sel Torq Ctrl Only
Parameters::Motor Control::Spd Loop Settings
BOOL
FALSE
ALWAYS
TECHNICIAN
01581
0528
Direct Input Select Parameters::Motor Control::Spd Direct Input
USINT
(enum)
0
0:NONE
1:ANIN1
2:ANIN2
ALWAYS TECHNICIAN
01583
0529
Direct Input Ratio
Parameters::Motor Control::Spd Direct Input
REAL
1.0000
-10.0000 to 10.0000
ALWAYS
TECHNICIAN
01585
0530
Direct Input Pos Lim
Parameters::Motor Control::Spd Direct Input
REAL
110.00
-110.00 to 110.00
%
ALWAYS
TECHNICIAN
01587
0531
Direct Input Neg Lim
Parameters::Motor Control::Spd Direct Input
REAL
-110.00
-110.00 to 110.00
%
ALWAYS
TECHNICIAN
01589
0533
Total Spd Demand RPM
Parameters::Motor Control::Spd Loop
Diagnostics
REAL x.xx -100000.00 to 100000.00 RPM
NEVER TECHNICIAN
01593
0534
Total Spd Demand %
Parameters::Motor Control::Spd Loop
Diagnostics
REAL x.xx -200.00 to 200.00 % NEVER TECHNICIAN
01595
0535
Speed Loop Error
Parameters::Motor Control::Spd Loop
Diagnostics
REAL x.xx -400.00 to 400.00 % NEVER TECHNICIAN
01597
0536
Speed PI Output
Parameters::Motor Control::Spd Loop
Diagnostics
REAL x.xx -500.00 to 500.00 % NEVER TECHNICIAN
01599