D-44 Parameter Reference
AC30V series Variable Speed Drive
Flycatching
Parameters::Motor Control::Flycatching
This feature performs a directional speed search. It allows the Drive to seamlessly catch a spinning motor before controlling the motor to the
desired setpoint. This is especially useful for large inertia fan loads, where drafts in building air ducts can cause a fan to `windmill’.
PNO Parameter Descriptions
0310 VHz Flying Start Enable
Enable flycatching in V/Hz control mode when TRUE
0311 VC Flying Start Enable
Enable flycatching in Vector control mode when TRUE
0312 Flying Start Mode
Mode of operation - V/Hz control
Enumerate Value: Flying Start Mode
0: Always
1: Trip or Power up
2: Trip
0313 Search Mode
The type of speed search carried out by the flycatching sequence.
Enumerated Value : Search Mode
0 : BIDIRECTIONAL
1 : UNIDIRECTIONAL
0314 Search Volts
Only under VHz control
The percentage level of the search volts applied to the motor during the speed search phase of the flycatching sequence. Increasing
this parameter improves the accuracy of the discovered motor speed but increases the braking influence of the speed search on the
rotating motor.
0315 Search Boost
Only under VHz control
The level of search boost applied to the motor during the speed search phase of the flycatching sequence.
0316 Search Time
Only under VHz Control
www.comoso.com

Table of Contents

Other manuals for Parker AC30 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker AC30 series and is the answer not in the manual?

Parker AC30 series Specifications

General IconGeneral
Control ModesClosed-loop vector
FeedbackEncoder
Operating Temperature0 to 40°C (32 to 104°F) standard, -20 to 50°C (-4 to 122°F) with derating