C-27 Compliance
AC30V series Variable Speed Drive
Harmonic Information
Supply Harmonic Analysis (Frame D - Normal Duty)
Assumptions: Rsce = 120 at 400V where Q
1n
is the rated rms value of the fundamental voltage of the supply
transformer. The results conform to IEC61000-3-12:2011.
(kW)
1.1 1.5 2.2 3.0 4.0 5.5
1.1 1.5 2.2 3.0 4.0 5.5
Typical Motor
83 83 83 83 83 83 83 83 83 83 83 83
Total RMS
Current (A)
2.73 3.75 4.92 6.19 7.87 10.47
23 0.065 0.088 0.130 0.178 0.236 0.32 * THD
) % 70.2 70.7 59.8 50.8 43.7 37.8
* (Total Harmonic Distortion)