EasyManua.ls Logo

Parker AC30 series - Slip Compensation

Parker AC30 series
453 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D-104 Parameter Reference
AC30V series Variable Speed Drive
Slip Compensation
Parameters::Motor Control::Slip Compensation
Designed for VOLTS/Hz motor Control Mode.
The slip compensation function allows the Drive to maintain motor speed in the presence of increased load.
PNO Parameter Descriptions
0354 Slip Compensatn Enable
Enable/Disable slip compensation
0356 SLP Motoring Limit
Maximum compensated speed in motor control
0357 SLP Regen Limit
Maximum compensated speed in regen mode
Functional Description
Based on the rated speed, the no load speed and the rated load of the motor, the Slip Compensation feature adjusts the demand frequency to
compensate for any speed reduction resulting from the load.