Technical Specifications F-11
AC30V series Variable Speed Drive
FRAME D INTERNAL DYNAMIC BRAKE SWITCH
Product Code
Motor Power
(kW/hp)
Brake Switch
Peak Current (A)
Peak Brake
Dissipation (kW/hp)
Brake Switch
Continuous Current
(A)
Continuous Brake
Dissipation
(kW/hp)
Minimum
Brake Resistor
Value (
)
400V Build Variant: 380-480V ±10%, 50/60Hz +5% DC link brake voltage: 765V
31V-4D0004… 1.1/1.5 1.5A 1.1/1.5 1 0.75/1 520
31V-4D0005… 1.5/2 2.2A 1.7/2.3 1.4 1.1/1.5 355
31V-4D0006… 2.2/3 2.9A 2.3/3 2 1.5/2 260
31V-4D0008… 3/ 4.3A 3.3/4.5 2.9 2.2/3 177
31V-4D0010… 4/5 5.9A 4.5/ 3.9 3/ 130
31V-4D0012… 5.5/7.5 7.8A 6/7.5 5.2 4/5 98
FRAME E INTERNAL DYNAMIC BRAKE SWITCH
Product Code Motor Power
(kW/hp)
Brake Switch
Peak Current (A)
Peak Brake
Dissipation (kW/hp)
Brake Switch
Continuous Current
(A)
Continuous Brake
Dissipation
(kW/hp)
Minimum
Brake Resistor
Value (
)
400V Build Variant: 380-480V ±10%, 50/60Hz +5% DC link brake voltage: 765V
31V-4E0016… 7.5/10 10.8A 8.25/11.25 7.2 5.5/7.5 71
31V-4E0023… 11/15 14.7A 11.25/15 9.8 7.5/10 52
FRAME F INTERNAL DYNAMIC BRAKE SWITCH
Product Code Motor Power
(kW/hp)
Brake Switch
Peak Current (A)
Peak Brake
Dissipation (kW/hp)
Brake Switch
Continuous Current
(A)
Continuous Brake
Dissipation
(kW/hp)
Minimum
Brake Resistor
Value (
)
400V Build Variant: 380-480V ±10%, 50/60Hz +5% DC link brake voltage: 765V
31V-4F0032… 15/20 21.5A 16.5/22.5 14.4 11/15 35
31V-4F0038… 18/25 29.4A 22.5/30 19.6 15/20 26