Compliance C-34 
AC30V series Variable Speed Drive 
CANADIAN COMPLIANCE 
This product has been approved by Intertek Testing and Certification Ltd (ETL) to Canadian Standard CSA 22.2 No. 14, Standard for Industrial 
Control Equipment and Canadian Standard CSA 22.2 No. 14, Industrial control Equipment. 
     
NORTH AMERICAN AND CANADIAN COMPLIANCE INFORMATION 
Motor Base Frequency 
PMAC and Induction motor modes are identical. 
Drive Switching Frequency  Maximum Output Frequency 
590Hz (1000Hz subject EU Export Control Annex I to Council Regulation (EC) No. 428/2009) 
590Hz (1500Hz subject EU Export Control Annex I to Council Regulation (EC) No. 428/2009) 
590Hz (1500Hz subject EU Export Control Annex I to Council Regulation (EC) No. 428/2009) 
 
Drive Protection 
Branch Circuit Protection 
It is recommended that UL Listed non-renewable cartridge fuses (JDDZ) or UL Listed renewable cartridge fuses (JDRX) are installed upstream of 
the drive.  Refer to Appendix F: “Technical Specifications” - Power Details for recommended fuse ratings. 
 
Solid-State Motor Overload Protection 
This product provides Class 10 motor overload protection. The maximum internal overload protection level (current limit) is 180% for 3 seconds, 
in addition Heavy Duty mode is 150% for 60 seconds and Normal Duty mode  is 110% for 60s in. Refer to Appendix D Programming – Current 
Limit for user current limit adjustment information. 
 
An external motor overload protective device must be provided by the installer where the motor has a full-load Ampere rating of less than 50% of 
the drive output rating or when the Disable Stall trip is enabled; or when the Stall time parameter is increased above 480 seconds (refer to 
Appendix D Programming : Stall Trip). 
 
Motor over temperature sensing is not provided by the product unless the external temperature sensor is connected to the motor thermistor input 
on the GPIO option.  When the GPIO option is not fitted an external motor over temperature device is required.