EasyManua.ls Logo

Parker AC30 series - Parameter Summary

Parker AC30 series
453 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Modbus TCP A-8
AC30V series Variable Speed Drive
Parameter Summary
The following parameters are relevant to the Modbus TCP.
PNO Parameter Descriptions
0939
Maximum Connections
Type: USINT
Default: 0
Base Communications Modbus TCP parameter.
Sets the maximum number of Modbus clients allowed. If set to zero, then no connections will be allowed.
Range Writable Saved Config
0
3
0940
High Word First
Type: BOOL
Default: FALSE
Base Communications Modbus TCP parameter.
If set to TRUE, the most significant word of a 32-bit parameter will be mapped to the first register, and the least significant word to the
next register.
Range Writable Saved Config
FALSE
TRUE
0941
Modbus Timeout
Type: TIME
Default: 3.0 seconds
Base Communications Modbus TCP parameter.
Sets the process active timeout
Range Writable Saved Config
0
65.0 seconds
www.comoso.com

Table of Contents

Other manuals for Parker AC30 series

Related product manuals