Modbus TCP A-8
AC30V series Variable Speed Drive
Parameter Summary
The following parameters are relevant to the Modbus TCP.
PNO Parameter Descriptions
0939
Maximum Connections
Type: USINT
Default: 0
Base Communications Modbus TCP parameter.
Sets the maximum number of Modbus clients allowed. If set to zero, then no connections will be allowed.
Range Writable Saved Config
0
3
0940
High Word First
Type: BOOL
Default: FALSE
Base Communications Modbus TCP parameter.
If set to TRUE, the most significant word of a 32-bit parameter will be mapped to the first register, and the least significant word to the
next register.
Range Writable Saved Config
FALSE
TRUE
0941
Modbus Timeout
Type: TIME
Default: 3.0 seconds
Base Communications Modbus TCP parameter.
Sets the process active timeout
Range Writable Saved Config
0
65.0 seconds
www.comoso.com

Table of Contents

Other manuals for Parker AC30 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker AC30 series and is the answer not in the manual?

Parker AC30 series Specifications

General IconGeneral
Control ModesClosed-loop vector
FeedbackEncoder
Operating Temperature0 to 40°C (32 to 104°F) standard, -20 to 50°C (-4 to 122°F) with derating
ProtectionOvercurrent, Overvoltage, Undervoltage
CommunicationRS485

Related product manuals