Installation 4-30
AC30V Variable Speed Drive
TERMINAL BLOCK WIRE RANGE
Wire sizes for Europe should be chosen with respect to the operating conditions and your local National Electrical Safety Installation
Requirements. Local wiring regulations always take precedence. For North American UL wire sizes refer to Appendix C: “Compliance” -
Requirements for UL Compliance.
Power Terminals
(minimum/maximum acceptance for aperture)
31V-4D0004- ...
31V-4D0005- ...
31V-4D0006- ...
31V-4D0008- ...
31V-4D0010- …
31V-4D0012- …
0.05 - 6 mm
2
M4 ring crimp 0.229 - 2.5 mm
2
31V-4E0016- ...
31V-4E0023- …
0.05 – 6 mm
2
M4 ring crimp 0.229 - 2.5 mm
2
31V-4F0032- …
31V-4F0038- …
1 - 10 mm
2
(*16 mm
2
) M4 ring crimp 0.229 – 2.5 mm
2
31V-4G0045- …
31V-4G0060- …
31V-4G0073- …
1.3 – 25 mm
2
M5 ring crimp 0.229 – 2.5 mm
2
31V-4H0087- …
31V-4H0105- …
31V-4H0145- …
M8 post, accepting crimps or lugs up to width 26.5mm
(minimum 25mm
2
wire size)
M8 ring crimp 0.229 – 2.5 mm
2
31V-4J0180- …
31V-4J0205- …
31V-4J0260- …
M8 post, accepting crimps or lugs up to width 32mm
(minimum 25mm
2
wire size)
M8 ring crimp
Up to width 26.5mm
0.229 – 2.5 mm
2
*The larger wire size can be used provided a crimp is fitted to the wire