D-116 Parameter Reference 
AC30V series Variable Speed Drive 
Torque Limit 
Parameters::Motor Control::Torque Limit 
 
This function allows you to set the maximum level of motor rated torque which is allowed before torque limit action occurs. 
If the estimated motor torque is greater than the Actual Pos Torque Lim value, the motor speed is controlled to maintain the torque at this level. 
A similar situation occurs if the estimated motor torque is less than the Actual Neg Torque Lim value. 
 
The torque limit function has separate positive and negative torque limits. In addition, a symmetric main torque limit is also provided. 
The lowest positive and negative torque limits (including any current limit or inverse time current limit action) is indicated in the Actual Pos 
Torque Lim and Actual Neg Torque Lim diagnostic. These values determine the absolute motor torque limits. 
 
PNO  Parameter Descriptions 
0415  Positive Torque Lim 
This parameter sets the maximum allowed level of positive motor torque. 
0416  Negative Torque Lim 
This parameter sets the maximum allowed level of negative motor torque 
0417  Main Torque Lim 
This parameter sets the symmetric limit on the maximum allowed motor torque. 
0418  Fast Stop Torque Lim 
This parameter sets the torque limit used during a Quickstop. 
0419  Symmetric Torque Lim 
When TRUE, the 
 is forced to reflect the 
 parameter. 
0420  Actual Pos Torque Lim 
This diagnostic indicates the final actual positive torque limit including any current limit or inverse time current limit action. 
0421  Actual Neg Torque Lim 
This diagnostic indicates the final actual negative torque limit including any current limit or inverse time current limit action.